cet-14697		cet-14697		6	.pdf	application/pdf	2800	77	36	In particular, the effectiveness of two barriers have been analyzed: • Separation distance between BESS units and electric transformer • Structural characteristics of the BESS walls The analyses for the transformer fire scenario showed that the temperatures of the external side of the most exposed wall reached about 250 °C due to the interposed separation distance (5 m); the presence of an intermediate technical volume and the thermal insulation of the walls avoided a significant rise of the air temperature inside the batteries room, that reached a temperature of about 30 °C. This approach is consistent with what has already been developed, again for BESS systems, and is available in the relevant scientific literature, which shows some applications of the Bow-Tie methodology to similar cases.	cache/cet-14697.pdf	txt/cet-14697.txt