Microsoft Word - 6-2754_s_ETASR_V9_N4_pp4342-4348


Engineering, Technology & Applied Science Research Vol. 9, No. 4, 2019, 4342-4348 4342  
  

www.etasr.com Le & Vu: Performance Evaluation of a Generator Differential Protection Function for a Numerical Relay 

 

Performance Evaluation of a Generator Differential 

Protection Function for a Numerical Relay 
 

Kim Hung Le 

The University of Danang - University of Science and 
Technology 

Da Nang, Vietnam 

lekimhung@dut.udn.vn 

Phan Huan Vu 

Central Power Corporation - Central Electrical Testing 
Company Limited 
Da Nang, Vietnam 

vuphanhuan@gmail.com 
 

 

Abstract-This paper describes the advantages and disadvantages 

of a generator differential protection relay system which uses 

double slope characteristics of Areva P343, ABB REG670, 

SEL300G and GE G60. A Buon Tua Srah Hydropower Plant in 

Vietnam was selected as an example for the relay setting 

calculations of these characteristics. The performance of the 

introduced relay model was tested at various fault conditions in 

Matlab/Simulink. The results apply to the problems of solving the 

performance of the relay accurately and with reliable differential 
protection against internal faults, and keeping the generator 

stable on all external faults and in normal conditions. The 

simulation simplifies the process of selecting the relay and 

protection system. This can improve the quality of the protection 

system design early, thereby reducing the number of errors 
found later in the operation. 

Keywords-generator; differential protection function; slope 1; 

slope 2; Matlab/Simulink 

I. INTRODUCTION  

The synchronous generator is the most important element 
of a power system. Generator faults are considered serious 
since they may cause severe and costly damages to insulation, 
windings, and stator core. The large short circuit currents cause 
large current forces, which can damage other components in 
the power plant, such as the turbine and the generator-turbine 
shaft, or even initiate explosion and fire. In addition, if the 
generator is tripped in connection to an external short circuit, it 
can give an increased risk of power system collapse. To limit 
the damages in connection to a stator winding short circuits and 
abnormal operating conditions, generators need to be protected 
as much as possible by a proper protection system [1]. 
Nowadays, there are a variety of numerical different protective 
relays on the market which include many functions in one unit, 
and provide metering, communication, and generator 
protection. These protective relays help us to simplify the 
protection implementation in circuit design and setting 
calculations. Although there is quite an agreement among 
protection engineers as to what constitutes the necessary 
protection and how to provide it, there are still many 
differences of opinion in certain areas. As protection system 
complexity increases with IEDs connected to the hydropower 
plant, the evaluation of effective protection relay becomes a 

need for well-designed algorithms that can allow or deny 
arranged trip of generator, field circuit, and neutral breakers (if 
used) through a lockout relay based on decisions, to enable 
fault isolation. Among them, generator differential protection 
function (F87G) is one of the most critical protection 
applications. It is mainly employed for the protection of stator 
windings of generator against earth faults and phase-to-phase 
faults. It is also of great importance that the F87G does not trip 
for external faults when the large fault current is fed from the 
generator. The need to evaluate F87G with individual different 
characteristics has been well known to generator protection 
engineers. The techniques, methods and practices to provide 
this coordination are well established but scattered in various 
textbooks, papers, and in manufacturer’s user manuals [2].  

Author in [1] evaluated the performance of the F87G of the 
SEL 300G generator protection relay which was employed to 
protect the particular low resistance grounded 555MVA 
generator represented in the real-time simulation model of the 
RSCAD generic software. Authors in [3] considered the F87G 
and simulated this function using Simulink. Authors in [4] 
described the effects of damages in secondary circuits and the 
influence on disoperation of differential protection Micom 
P633 of the unit generator–transformer in Simulink. Authors in 
[5] conducted performance evaluation of the F87G by using a 
dynamic model of ATP/EMTP software for a large steam 
turbine synchronous generator. Authors in [6] used ATP-
EMTP package to simulate and generate fault data which were 
processed in Matlab to implement relay logic for detecting 
internal faults in the stator windings of F87G. Authors in [7] 
used an ANFIS algorithm in Simulink to design a F87G. The 
technical manuals of Schneider P343, ABB REG670, 
SEL300G and GE G60 relay protections are in [9, 11, 14, 15] 
respectively. The works on detailed settings guidance [10, 12, 
13, 16] allow protective relaying engineers to have a clear 
understanding of which methods are available on every relay 
protection, what input parameters are required for each method 
and the expected results of each. In practice, the worst 
condition of unbalanced secondary currents is realized when 
the current transformer (CT) in the faulted circuit is completely 
saturated and none of the other CTs suffers a reduction in ratio. 
It is a universal differential protection problem for an unwanted 
trip of the generator [8]. Besides, there is a possibility that 

Corresponding author: Phan Huan Vu 



Engineering, Technology & Applied Science Research Vol. 9, No. 4, 2019, 4342-4348 4343  
  

www.etasr.com Le & Vu: Performance Evaluation of a Generator Differential Protection Function for a Numerical Relay 

 

someone with unauthorized access might infiltrate the relay and 
reconfigure incorrect settings instructing it to release a false trip 
signal without the existence of a fault. When these types of 
misoperation risks go undetected, it is very easy for operators 
to mistakenly believe that their relay protection is secure. 
Hence, the question that operators need to ask is: “How 
confident am I that my relay protection is reliable and secure?”. 
Therefore, the purpose of this paper is to provide a single 
document that can be used to calculate relay setting parameters 
with multi-vendors, to answer the most frequently asked 
questions about F87G considering the Buon Tua Srah 
Hydropower Plant in Vietnam. In addition, a Matlab/Simulink 
model to check four generator differential characteristics to the 
plant will be checked while simulating fault cases. It will equip 
the reader with the knowledge to choose the most suitable 
vendor for his or her project. 

II. GENERATOR DIFFERENTIAL PROTECTION FUNCTION 

This section shows how an F87G characteristic is 
constructed and how it works. Selection rules for setting 
parameters are discussed. As an example, Figure 1 illustrates 
the schematic diagram for the implementation of the main 
generator protection of a Buon Tua Srah Hydropower Plant. 
Line side CTs and neutral side CTs are both ends of the stator 
winding which are wye-connected. The F87G relies on 
measurements of the currents of the protected generator in 
order to calculate differential and biased currents which are 
then utilized to make tripping decisions. On low-impedance 
grounded machines, this scheme can detect phase-to-phase, 
phase-to-ground, and three-phase faults. Equations (1) and (2) 
show the mathematical definition of the differential and biased 
currents, respectively, which are employed by various vendors 
such as Schneider, ABB, SEL, and GE. 

 

 
Fig. 1.  Differential protection relay connection with a generator.  

The differential current: ||
_

2

_

1 III DIFF +=   (1) 

The biased current: 
2

||||
_

21

_

II
I

BIAS

+
=  (2) 

Based on these values of IBIAS and of IDIFF, the trip/restrain 
characteristics are applied in the vendors of protection relay 
which has a three-step shape (two slopes and one pickup level) 
as in Figure 2. The differential current pickup setting (IS1, Idmin, 
87OP, Pickup) should avoid the maximum unbalance current 
under normal load condition which is mainly caused by CT 
error, the normal current error (KCT_ERR) must be less than 5% 
the operating current for the 5P20 type CT, and we should 

multiply by a reliable coefficient KREL that is normally equal to 
1.5. This setting can be set as low as 5% of the rated generator 
current, to provide protection for as much of the winding as 
possible [10]. 

 

 

  

Fig. 2.  Differential protection characteristics 

Slope1 setting (K1, SlopeSection2, SLP1, and Slope1) is set 
to ensure sensitivity to internal faults at normal operating 
current levels. The criterion for setting this slope is to allow 
maximum expected CT mismatch error when operating at 
maximum permitted current. In this case, it combines the 
KCT_ERR. The relay pickup accuracy (KRELAY_ERR) can be 
obtained from the instruction manual of the relay, and an 
operating margin (KMARGIN) of 5% is typically provided in order 
to increase the security of the differential protection scheme 
[13]. The purpose of the Slope2 setting (K2, SlopeSection3, 
SLP2, Slope2) is to increase the security of the differential 
protection scheme during heavy through-fault conditions. It can 
result in severe saturation of a CT. When a CT saturates, it can no 
longer trustworthy reproduce the primary current with a scale 
factor on the secondary side of the CT. As a result, a very high 
differential current may be obtained under this fault condition. 
The Slope2 setting is typically set higher than the Slope1 setting. 
Relay setting calculation is an important task for a power plant 
before operating. The parameter in this calculation is used for 
the setting of the relay protection equipment of the power plant. 
Choosing the slope of a differential relay has been more art 
than science. Manufacturer’s guidelines tend to be qualitative 
or empirical in nature. They are based on the manufacturer’s 
experience and knowledge of his/her design [9], as shown in 
the above F87G using trip/restrain characteristics. We can 
calculate detailed adjustable settings by using the generator 
parameters as in Table I [10].  

A. Schneider P343 [11, 12] 

Is1 is calculated to avoid maximum unbalance under 
normal load and the K1 should be 0% to assure the sensitive 
under normal operating current. 

. .
1

1.5 (2 0.05) 2116.5
0.127,

2500

REL ERR CT G N
S

K K I
I

CT

× × × × ×
= = =  

so, 0.2A is proper. 

IBIAS 

Slope2
IDIFF 

Pickup 

Slope1 

Break1 Break2 

(d). GE G60 

IRT 
Slope1 

Slope2 

IOP 

O87P 

IRS1 

U87P 

(c). SEL 300G 

Zone3 

Slope 

Section2 

Slope  

Section3 

IDIFF 

IBIAS 

Idmin 

EndSection1 EndSection2 

Zone1 

Zone2 

(b). ABB REG670 

IBIAS 

IDIFF 

IS1
K1 

IS2 

K2 

(a). Areva P343 



Engineering, Technology & Applied Science Research Vol. 9, No. 4, 2019, 4342-4348 4344  
  

www.etasr.com Le & Vu: Performance Evaluation of a Generator Differential Protection Function for a Numerical Relay 

 

The Is2 should be the same with CT rating current or 
generator’s 120% nominal current. CT rating current is 2500A, 
so Is2=2500A, the secondary value is Is2=1A. The K2 is 
normally to avoid external max unbalance current under max 
throughout fault near protection zone. This max unbalance 
current can be calculated according to: 

IUnb.Max=KREL×KAP×KCC× KERR.CT×I
(3)

Max  (3) 

where the external three phase short circuit current is: 

(3) .

"

2116.5
4.045

0.2093 2500

G N
Max

d

I
I

X CT
= = =

××
. The CT type factor KCC 

should be 0.5 when same type CT for each side, or be 1 when 
different type CT for each side. In this paper, we select 0.5. 

The non-periodic factor is KAP=1.5~2.0. In this paper, we 
select 2.0. So: IUnb.Max=1.5×2×0.5×0.1×4.045=0.6068. 

According to the equation:  

. 1

(3)
2

0.6068 0.2
2 0.1336

4.045 1

Unb Max S

Max S

I I
K

I I

− −
= = =

−−
, we suggest 

selecting K2=0.2. The F87G operates when IDIFF exceeds Is1 
and the percentage of IBIAS, defined by a slope setting (K1, K2). 
It can be calculated using the following: 

IDIFF>K1×IBIAS+IS1 where IBIAS ≤IS2 

IDIFF >K2×IBIAS–(K2−K1)×IS2 +IS1 where IBIAS>IS1 

TABLE I.  PARAMETERS OF BUON TUA SRAH HYDROPOWER PLANT 

Parameters Values 

Rated capacity 50.6 MVA 

Normal Current IG.N 2116.5A 

Rated Voltage 13.8kV 

Frequency 50Hz 

PT ratio of the terminal of the 

generator 

13.8 0.11 0.11
0.11

3 3 3  
Line CT ratio 2500/1 

Neutral CT ratio 2500/1 

Rated current secondly 0.8466A 

Synchronous reactance Xd 99.28% 

Transient reactance X’d 28.27% 

Sub Transient reactance X’’d 20.93% 

Synchronous reactance Xq 62.88% 

Negative reactance X2 23.60% 

Static negative current I2∞ 250A 

Transient negative current I
2
2t 40s 

KRELAY_ERR 
SEL300G is 2%, G60 is 1%, 

P434 is 5%, and REG670 is 2% 

 

B. ABB REG670 [9, 10] 

The pick-up value (Idmin) is:  

. .
min

1.5 (2 0.05) 2116.5
0.127

2500

REL ERR CT G N
d

K K I
I

CT

× × × × ×
= = =  

We set Idmin=0.2IG.N. 

In Section1, the risk of false differential current is very low. 
This is the case, EndSection 1 is set to experience value: 

.
0.5 0.5 2116.5

Sec 1 0.4233
2500

G N
I

End tion
CT

× ×
= = =  

A SlopeSection2 is proposed to be set to 30%. Breakpoint 2 
set to experience value: 

.
3 3 2116.5

Sec 2 2.5398
2500

G N
I

End tion
CT

× ×
= = =  

SlopeSection3=80%. It is supposed to cope with false 
differential currents related to current transformer saturation. 
The F87G operates when IDIFF exceeds a threshold Idmin and a 
percentage of IBIAS: 

( )2 1  
when 1 2

DIFF dmin BIAS

BIAS

I I SlopeSection I EndSection

Endsection I EndSection

> + × −

≤ ≤

 
    

( )
( )

  2 2  S 1

  3  2  ]

when 2

[
DIFF dmin

BIAS

BIAS

I I SlopeSection EndSection End ection

SlopeSection I EndSection

I EndSection

> + × −

+ × −

≥

 

C. SEL300G [13, 14] 

The Slope1 setting can be calculated as: 

1 2
_ _CT ERR RELAY ERR MARGIN

SLP I K K= × + +    (4) 

SLP1=2×5%+2% +5%=17%, so 20% is proper. O87P 
setting is calculated using the guidance shown in equation: 
O87P=0.5∗SLP1=0.1 

The SLP2 setting is fixed to 100%, the turning point 
between Slope1 and Slope2 defined by the value IRS1 is fixed 
to 3.0 per unit. The purpose of the Unrestrained Differential 
Element Pickup Setting (U87P) is to detect the very high 
differential current that clearly indicates a fault inside the 
differential protection zone. The U87P setting is set to 10 per 
unit as recommended by the relay manufacturer. The criteria 
for internal and external faults can be seen from the differential 
characteristic and are described below: 

87  where 87 1/
DIFF BIAS
I O P I O P SPL> ≤  

1
1 when 87 1/

DIFF BIAS BIAS RS
I I SLP O P SPL I I> × < <  

( ) 12 1  2 when  DIFF BIAS B RBI S SA IASI I SLP SLP SLP I I I> × + − × ≥  

D. GE Multilin G60 [15, 16] 

. . 1.5 0.02 2116.5 0.025398
2500

REL er n G NK I IPickup
CT

× × × ×
= = = , so 

0.1A is proper. Slope1 is set at 15% starting from 0.04 (RC). 
The Break1 setting should greater than the maximum overload 
expected for the machine: 

.1.05 1.05 2116.51 0.88893
2500

G NIBreak
CT

× ×
= = = , so it is set at 1.2 

Slope2 is set at 80 %. 

The Break2 setting is set at 3 or 4. It provides security from 
misoperation for maximum fault and resulting maximum CT 
error condition. The criteria for internal and external faults can 
be seen from the differential characteristic and are described 
below: 



Engineering, Technology & Applied Science Research Vol. 9, No. 4, 2019, 4342-4348 4345  
  

www.etasr.com Le & Vu: Performance Evaluation of a Generator Differential Protection Function for a Numerical Relay 

 

 where 1/
DIFF BIAS
I Pickup I Pickup Slope> ≤  

1 when 1 1 /
DIFF BIAS BIAS
I Slope I Pickup Slope I Break> × < <  

2 3
0 1 2 3  ≥ + × + × + ×DIFF BIAS BIAS BIASI C C I C I C I  

when 1 2, where:< <BIASBreak I Break  

2 2

0 3

2 ( 1 2) 1 2

( 1 2)

Slope Slope Break Break
C

Break Break

× − ×
=

−

×
 

2 2

1 3

2 1 ( 1 1 2 4 2 )

( 1 2)

Slope Break Break Break Break Break
C

Break Break

× × + × + ×
=

−
     

    
2 2

3

1 2 (4 1 1 2 2 )

( 1 2)

Slope Break Break Break Break Break

Break Break

× × × + × +
−

−
 

2 2

2 3

2 ( 1 2) ( 1 1 2 2 )

( 1 2)

Slope Slope Break Break Break Break
C

Break Break

× − × + × +
=

−

( ) ( )
3 3

2 1 1 2

( 1 2)

Slope Slope Break Break
C

Break Break

− × +
=

−
 

and IDIFF>Slope2×IBIAS when IBIAS≥Break2 

All setting parameter results are calculated based on the 
best manufacturer practices that are adjusted to compensate for 
CT ratio error mismatch and CT response via a dual slope 
characteristic typically as shown in Figure 7. 

Review: The numerical algorithm of the F87G is very 
similar to motor differential protection. It is also principally 
simpler than that of the power transformer differential 
protection. No phase shifts, and no transformation ratios, typical 
for power transformers, must be numerically allowed for. The 
suggested protection for instantaneous and sensitive protection 
for generator internal faults is presented in [17]. The variable 
slope percentage differential relay is a widely used form of 
differential relaying for generator protection. In this type of 
relay, the percentage slope characteristic may vary from about 
10% at low values of through current up to 100% or more at 
high values of through current. A P434 is more sensitive than 
another relay with K1=0% during light internal faults and 
relatively low sensitivity (K2=20%) during heavy external 
faults. 

III. POWER SYSTEM UNDER STUDY 

Matlab/Simulink tool is useful for the basic understanding 
of power system protection, particularly for new engineers. It 
helps them to model the F87G system behavior under normal 
and fault conditions. In this section, the F87G performance is 
tested on the 13.8kV, 50.6MVA synchronous generator, 
connected with 220kV through a 51MVA, D11Yn step-up 
transformer as shown in Figure 3. 

A. The Generator 

The generator is represented by its impedance and an AC 
source, required for the system supply. It is located at the point 
where one side can easily be grounded. A resistor of 0.5Ω, 

which exists in the actual grounded generator neutral, is not 
represented. This assumption does not have a significant 
influence on the study. 

 

 

Fig. 3.  Power system model 

B. Current Transformer Models 

Current phasors at both ends of stator windings are 
2500/1A 5P20 30VA which are performed the current 
transformer excitation test, measured the CT winding resistance 
and CT current-ratio automatically by The Vanguard EZCT-
2000 test set in Central Electrical Testing Company Limited. 
All of the EZCT’s test leads can be connected to the CT output 
terminals, eliminating the need for lead switching during 
testing. Test voltage output is automatically raised and lowered 
by the EZCT without any operator intervention. Once the test is 
completed, test results can be printed and excitation curves can 
be plotted on the built-in 4.5-inch wide thermal printer as in 
Figure 4.  

 

 

Fig. 4.  V-I curve of CT 2500/1 A 

Knee Type IEC 10/50 standard [18]: Vpk=1401.44V, 
Ipk=0.0124A, CT ratio: 2485.885/1A, Error: 0.5646%, Ex 
V=99.6V, Ex I=0.02A, Phase angle: 0.120, CT Pole: In Phase, 
and Winding Res: 13.94Ω. 

The proposed mathematical current transformer model is 
shown in Figure 5 and is based on the CT Saturation Theory 
and Calculator presented by the IEEE Power System Relaying 
and Control Committee (PSRC) and the practical testing results 
of CT by Vanguard EZCT-2000 test set above (See [19] for 
more details). 



Engineering, Technology & Applied Science Research Vol. 9, No. 4, 2019, 4342-4348 4346  
  

www.etasr.com Le & Vu: Performance Evaluation of a Generator Differential Protection Function for a Numerical Relay 

 

 
Fig. 5.  A mathematical current transformer model 

C. Different Protection Relay Model 

By performing the essential computations given in Section 
II, we got the four models of F87G relay (P343, REG670, 
SEL300G, G60) which are connected on CT’s secondary side 
at both ends of the generator (IL, IN). After that, these signals 
were calculated using recursive discrete Fourier transform 
algorithm. These are combined with setting parameters 
sending to S-function block. This block has been developed 
for detecting generator stator winding internal faults. If the 
output from the S-function block is equal to zero, this means 
that there is no fault in the stator winding of the generator, 
otherwise, the stator winding of the generator has a fault. The 
inside Simulink model of F87G block is shown in Figure 6. 

 

 

Fig. 6.  Differential protection relay P434 block 

D. Three Phase Fault Block  

Three phase fault block F1 and F2 generate fault types and 
fault resistance varying from 1Ω to 35Ω which are inside the 
protected zone, and out of the protected zone, respectively. 

IV. SIMULATION RESULTS 

After the building of the proposed model has been 
completed, it is ready to analyze the operation of F87G applied 
under three cases below. In the first case, the normal condition 
shows the phase current waveforms captured at both terminal 
IN=IL=2200A, CT Error ≈0%, IDIFF≈0A and all relays have not 

generated trip signal. The trajectory of the operating point can 
be seen by the relay lied the restrain zone (Figure 7). 

 

 

 

 
Fig. 7.  Current waves, CT error, trip signals and trajectory of operating 

point for normal condition 

In the second case, the internal fault occurs at 0.16s on the 
terminal of phase ‘ABG’ stator winding as shown in Figure 8. 
The phase currents captured at both terminals IN=2kA, IL=1kA 
and remain in the same phase, CT Error ≈0%, IDIFF≈8A. 
According to change in current waveforms during the fault, the 
trajectory of the operating point moves quickly into trip zone, 
which results in a tripping at 0.178s (REG670), 0.1832s 
(SEL300G and G60), 0.1835s (P434). In the third case, a three-
phase fault occurs at 0.1s on the terminal of a synchronous 
generator that is external to the stator winding. If the CTs have 
no error, then currents at both ends of stator windings remain in 
the same value and opposite phase, and IDIFF≈0A. 
Unfortunately, during fault conditions as shown in Figure 9, 
CTs do not always perform ideally, since core saturation may 
cause a breakdown of a ratio (IN=20kA, IL=1.8kA). Such core 
saturation usually from 0.13s to 0.15s is the result of a DC 
transient in the primary fault current, total burden impedance 
ZB=150Ω and may be aggravated by the residual flux left in the 
core by a previous fault. The trajectory of the operating point 
moves into the trip zone of P434, SEL300G, and REG670. 
After that, it comes back to the restrain zone at 0.23s. 
Therefore, in order to provide additional security against 
maloperations during this event, the relay incorporates 
saturation detection logic. When saturation is detected, the 



Engineering, Technology & Applied Science Research Vol. 9, No. 4, 2019, 4342-4348 4347  
  

www.etasr.com Le & Vu: Performance Evaluation of a Generator Differential Protection Function for a Numerical Relay 

 

element will make an additional check on the angle between 
the neutral and line current. If this angle indicates an internal 
fault then tripping is permitted. In this case, the generator does 
not trip because the differential relay does not a response to the 
fault since the fault happens out of the protected zone. 

 

 

 

 
Fig. 8.  Current waves, CT error, trip sinals and and trajectory of operating 

point for internal fault condition (ABG fault) 

Review: The simulation results show that under the no-fault 
condition and external fault then the relay does not trip; under a 
fault condition, the trip signal is taken. In another way the 
characteristic results are very sensitive to internal faults and 
insensitive to CT error currents during severe external faults. 

V. CONCLUSIONS 

In order to verify the deployed generator protection scheme 
is working as designed after field installation, this paper is 
discussed with a Buon Tua Srah Hydropower plant example. 
The paper provides calculation on appropriate a pickup 
threshold, slope and breakpoint settings for an F87G function 
available from today’s modern multifunctional generator 
protection IEDs such as P434, REG670, SEL300G, and G60. It 
also presents important aspects of generator protection system 
analyzing at different conditions which are simulated on a 
synchronous machine stator winding in Matlab/Simulink. This 
software shows the two CTs’ current waves, and the different 
and restraint current trajectories on the relay characteristics. It 
tells the user how far the different locus intrudes into the trip 
zone. According to the obtained results, it has been shown that 
the IEDs operate safe and reliable. 

 

 

 
Fig. 9.  Current waves, CT error, trip sinals and and trajectory of operating 

point for external fault condition (ABC fault) 

ACKNOWLEDGMENT 

The authors would like to thank the Central Electrical 
Testing Company Limited, Vietnam for allowing the use of the 
test record of current transformer, setting the calculations of 
Hydropower Plants used in this study. 

REFERENCES 

[1] Y. T. Huang, Investigating the Performance of Generator Protection 
Relays Using a Real-Time Simulator, MSc Thesis, University of 

KwaZulu-Natal, 2013 

[2] D. Reimert, Protection Relaying for Power Generation Systems, Taylor 
& Francis Group, 2006 

[3] M. V. Sudhakar, L. K. Sahu, “Simulation of Generator Protection using 

Matlab”, IEEE International Conference on Smart Technologies and 
Management for Computing, Communication, Controls, Energy and 

Materials, Chennai, India, August 2-4, 2017 

[4] K. Kadriu, G. Kabashi, L. Ahma, “Misoperation of the Differential 
Protection During the Dynamic Processes of Faults in the Secondary 

Protection Circuit. Differential Protection Modeling with MATLAB 
Software and Fault Simulation”, 5th WSEAS International Conference 

on Power Systems and Electromagnetic Compatibility, Corfu, Greece, 
August 23-25, 2005 

[5] W. Yousef, M. A. Elsadd, A. Y. Abdelaziz, M. A. Badr, “Performance 
evaluation of generator-transformer unit overall differential protection in 

large power plant”, International Journal on Power Engineering and 
Energy, Vol. 9, No. 3, pp. 869-877, 2018 

[6] N. W. Kinhekar, S. Daingade, A. Kinhekar, “Current Differential 

Protection of Alternator Stator Winding”, International Conference on 
Power Systems Transients, Kyoto, Japan, June 3-6, 2009 

[7] R. Mohemmed, A. Cakir, “Modeling and simulation of differential relay 

for stator winding generator protection by using ANFIS algorithm”, 
International Journal of Scientific & Engineering Research, Vol. 7, No. 

12, pp. 1668-1673, 2016 



Engineering, Technology & Applied Science Research Vol. 9, No. 4, 2019, 4342-4348 4348  
  

www.etasr.com Le & Vu: Performance Evaluation of a Generator Differential Protection Function for a Numerical Relay 

 

[8] IEEE, C37.102 Guide for AC Generator Protection, IEEE, 2006 

[9] ABB, Generator Protection REG670 Application Manual, ABB, 2012 

[10] ABB Engineering (Shanghai) Ltd, #1, #2 G-T UNIT Protection Setting 
Calculations for Buon Tua Srah Hydro Power Plant, ABB Engineering, 

2009 

[11] Schneider Electric, MiCOM P343 Generator Protection Relay-Technical 

Manual, Schneider Electric, 2011 

[12] Ecidi-Alstom Consortium, Cscs System Protection Parameter 
Calculation, Vnss4-C3-9-001 /A, Ecidi-Alstom Consortium, 2010 

[13] XJ Electricity Co., Generator Relay Protection Setting Calculation 

Instruction, XJ Electricity Co., 2010 

[14] SEL, SEL-300G Multifunction Generator Relay Instruction Manual, 
SEL, 2018 

[15] GE Digital Energy, G60 Generator Protection System-Instruction 

Manual, GE Digital Energy, 2015 

[16] GE Grid Automation, Application Book-CT Requirements for GE 
Multilin Relays, GE Grid Automation, 2016 

[17] I. Brncic, Z. Gajic, S. Roxenborg, Adaptive Differential Protection for 
Generators and Shunt Reactors, ABB Power Technologies AB, 2007 

[18] Central Electrical Testing Company Limited, “The test record of current 

transformer 2500/1A, 5P20 30VA, 04/17/2014”, 2014 

[19] K. H. Le, P. H. Vu, “Testing and Evaluation of Factors Affecting the 
Current Transformer Saturation”, Journal of Science and Technology, 

Thai Nguyen University, Vol. 189, No. 13, pp. 129-134, 2018 (in 
Vietnamese)