http://www.press.ierek.com ISSN (Print: 2357-0849, online: 2357-0857) International Journal on: Environmental Science and Sustainable Development DOI: 10.21625/essd.v2i1.26 Evaluation of Basement’s Thermal Performance against Thermal Comfort Model at Hot-arid Climates, Case Study (Egypt) Heba Hassan Kamel1,2, Daisuke Sumiyoshi2 1Department of Civil and Architecture Technology, Beni Suef University, Egypt 2Department of Urban Planning, Graduate School of Human Environment Studies, Kyushu University, Japan Abstract Reaching thermal comfort levels in hot-arid climates is becoming more difficult nowadays without the use of high energy consuming mechanical systems. Therefore, the need to use effective passive energy design techniques, such as earth-sheltered buildings, is becoming greater. This paper describes research, that uses monitoring and simulations, to evaluate basements’ thermal performance, which reached thermal comfort levels without active air-conditioning systems, despite the harsh climate condi- tions. The case study was conducted in Al Minya city, Egypt, which is known for its high diurnal range. The study calibrated a non-conditioned basement simulation model versus the monitored data to simulate its thermal performance. The greatest challenge was to calculate the ground temperature. To do this successfully, we used an iterative approach between packages of the Basement preprocessor and EnergyPlus/Designbuilder until reaching a convergence. The iterative method results showed significant agreement, between the measured and modeled data, with a corre- lation of 98 percent, and errors with mean bias error and normalized root mean square error of -1.0 and 7.6 percent, respectively. On the other hand, the EnergyPlus method, integrating the Xing approach, showed significantly di- vergent results between the simulated models versus the measured data. The calibrated model analysis evaluation, using the Fanger’s thermal comfort model, showed satisfactory results within the thermal comfort sensation range. The research results significance indicates that the precise customized detailed iterative method is essential to create the needed inputs which subsequently lead to near-to-actual outputs compared with other ground-contact simula- tion methods. In fact, the precise customized detailed iterative method approach may be used as a benchmark for simulators for easy and precise ground temperatures’ calculations and earth-sheltered buildings’ simulations. © 2019 The Authors. Published by IEREK press. This is an open access article under the CC BY license (https://creativecommons.org/licenses/by/4.0/). Peer-review under responsibility of ESSD’s International Scien- tific Committee of Reviewers. Keywords Thermal comfort; Basements’ Evaluation; Ground Temperature Calculation; Hot-arid Climates 1. Introduction Earth shelters can be defined as: “structures built with the use of earth mass against building walls as external ther- mal mass, which reduces heat loss and maintains a steady indoor air temperature throughout the seasons” (Anselm pg. 24 https://creativecommons.org/licenses/by/4.0/ Kamel / Environmental Science and Sustainable Development, ESSD 2012). With regards to that principle, we might consider the basements as one kind of the earth sheltering tech- nique (Hassan and Sumiyoshi, 2017; Heba, 2012; Ismail, Heba, Arima, Ahmed & Akashi, 2013). Carmody and Sterling analyzed the effect of Earth integration on heating and cooling in a conceptual way, for winter and summer performance. Moreover, providing regional design approaches based on different climate con- ditions (Carmody and Sterling 1985). Regarding the ground temperature profile variation with depth, many researchers developed their own numerical expression models to predict the heat flow inside the ground (Al-Temeemi and Harris, 2003; Derradji and Aiche, 2014; El-Din 1999; Janssen, Carmeliet, and Hens 2004; Lazzarin, Castellotti, and Busato 2005; Serageldin et al. 2015; Maja Staniec and Nowak, 2016). In terms of thermal comfort in underground spaces, some researchers developed a mathematical model for cal- culating the heat transfer, then calculated the thermal comfort improvements using Predicted Mean Vote (PMV). However, it was only a hypothetical model without actual measurements (Szabó and Kajtár, 2016). Anselm used fluid dynamics simulation program (Phonics-VR) to predict the energy savings in the earth-sheltered model as a whole building simulation (Anselm 2008). Later on, 2009 Ip and Miller monitored the thermal perfor- mance of an Earth ship, as a kind of earth-sheltered buildings (Ip and Miller 2009). However, simulations only or monitoring only is not enough for a complete vision of the issue, one should integrate both into a valuable research. The most innovative pieces of research performed a comparison between the measured and simulated data, using simulation programs with and/or without mathematical models to predict the boundary condition temperature, and simulate the whole building performance (Andolsun et al. 2011; Freney, Soebarto, and Williamson 2012; Kharrufa 2008; Kumar, Sachdeva, and Kaushik 2007; M. Staniec and Nowak 2011). The state of the art of this technique is retrieved from Kruis and Krarti’s research, they developed a numerical framework to improve foundation heat transfer calculations although it only simulates quadrilateral walls (KivaTM) (Kruis and Krarti 2016). This study proves that the iterative approach between the EnergyPlus and the Basement preprocessor packages, is more accurate and gives diverse options for simulating the building shape and volume, especially in the hot-arid climates like Egypt, although it still consumes a large amount of time in the simulation process. Regarding the chosen hot-arid climate, it is recommended to use the Earth-contact effect with buildings above ground. Besides, it could be integrated with the stack effect architectural means to improve the natural ventilation and air quality as a potential development of this technique. Regarding the direct solar gain effect, the under-roof rooms are the most to obtain radiant heat gain from the con- crete roof directed to the Sun. Therefore, we considered it as the worst case to compare it with the effect of the earth-contact. After the basement calibration, the researcher conducted comparisons between two hypothetical living zones using the same calibrated inputs; one on the roof level and the other one on the underground level, exactly the same as the previously calibrated basement (Hassan et al., 2014). Nomenclature Cp Specific heat capacity of each layer, J/(Kg- ºk) Tav Average monthly temperature, ◦C. K Thermal conductivity of each layer per unit area, w/(m-ºk). Tn Neutrality temperature (Tneutrality), ◦C. L Thickness of each layer, m. V Volume of each layer per unit area, m3. m Mass of each layer, Kg. Greek letters R Resistivity of each layer, ºk/w. ρ Density of each layer per unit area, Kg./m3. pg. 25 Kamel / Environmental Science and Sustainable Development, ESSD 2. Climate Analysis of the selected city in Egypt The research is focusing on the scope of Egypt’s climate zone as one of the hot arid climates. The dilemma was to choose the suitable city for the best earth-sheltered buildings’ application. After numerous weather data analysis using the (Climate Consultant 5.4) software, as shown in (Figs. 1, 2), the researcher found that Al Minya city has the highest temperature differences between day and night, and is one of the cities that has the highest temperature differences between winter and summer. As known, the most significant value of this technique is the energy preservation potential for the Earth. That is due to the natural principles of annual heat storage, large temperature differences between the internal ground temperatures and the corresponding outdoor air temperatures, and the good insulation form direct solar radiation. Under extreme conditions, the temperature difference between the outside air and the required comfort conditions for the interior environment, could reach 32◦C (Anselm 2012). Making the best use from the daily and seasonal fluctuations underground, therefore, the deeper the building is located, the less severe will be the variation. Because of the thermal storage potential of the soil which moderates the extreme daily and seasonal temperature variations, wherein energy from a day is transferred to night, and energy from one season is transferred to the next, as in the natural Principle of Annual Heat Storage (PAHS). For the previously mentioned explanation, choosing an extreme climate as a case study would show the great sig- nificance of this technique to save energy and to reach the thermal comfort limits easily without the use of any air-conditioning systems. Therefore, we chose Al Minya city with the most extreme climate in Egypt as a case study. Analyzing the thermal comfort with the Psychrometric chart using the Ecotect Weather Tool, the research finds that it is recommended for the design to have an exposed mass plus night purge ventilation, as shown in (Fig. 3) This will expand the comfort area to cover most of the measured temperatures (H Hassan et al. 2014). Therefore, it is expected that using the earth sheltering technique, will cover more comfort range at the chart. Going a step further with testing the ground temperatures at different depths (0.5, 2.0, 4.0 m.); if the earth-sheltered concept is used; we can gain much higher thermal comfort and stable conditions, as shown in (Fig. 4). Figure 1. Comparison between Al Minya and Cairo cities of the Dry Bulb Temp. Avg. Monthly. Al-Minya has the highest differences between summer and winter. Figure 2. Daily Dry Bulb Temp showing the hottest and coldest day. pg. 26 Kamel / Environmental Science and Sustainable Development, ESSD Figure 3. Psychometric Analysis for Al Minya City, showing hourly weather data and the small comfort area, and extreme high and low temperatures. The exposed mass + night purge ventilation will expand the comfort area to a wider range. Other actions have lower effects on covering the discomfort range. Figure 4. Predicting temperatures under the ground surface, at depths of 0.5, 2.0, 4.0 m. The stable thermal comfort conditions are high with more depths under a ground cover. 3. Method In this section, we described the measurements’ details with sensors, and the weather file compared with the outdoor measurements, then how we calculated the ground temperature and the basement’s calibration process, followed by the inputs at both Basement preprocessor and the DesignBuilder/EnergyPlus. 3.1. Measurements The research conducted measurements of temperatures and humidity outside and inside the building during three winter and three summer months from 1st. January to 27th. March, and from 1st. August to 25th. October, using (RH) sensors by the increment of (30 minutes) resolution (KN 2010). Measurements were adapted to the resolution of (1 hour) for the comparison purpose with the simulated models’ zone temperatures outputs. Measurements were taken at unconditioned basement gym, and at the last floor of the same building at a residential apartment, at an unconditioned living zone, and at a conditioned bedroom zone. Sensors were located at the height of (1.1 m.) from the slab level of both the basement and the last floor. The basement’s slab was located at (-2.7 m.) under zero level of the street. 3.2. Weather File We compared between the measured outdoor temperatures for the year of 2014; the year when the research was done; and the typical year weather file Egyptian Typical Meteorological Year (ETMY), which was developed for pg. 27 Kamel / Environmental Science and Sustainable Development, ESSD standards development and energy simulation by Joe Huang from data provided by U.S. National Climatic Data Center for periods of record from 12 to 21 years, all ending in 2003. Joe Huang and Associates, Moraga, California, USA. The location of the study is (Al Minya 623870). We found very slight differences between them at the study period. Therefore, we used the typical weather file for the simulation input and we used the measured temperatures of the six winter and summer months at the year of 2014 for comparison purpose only. Figure 5 shows a comparison at the measured periods (Fig. 5). Figure 5. A comparison between the typical year weather file, and the actual measurements’ temperatures for the year of 2014. The previous approach supports what Wasilowski and Reinhart had concluded from their research as they discov- ered that differences were very slight between the typical weather file and the measured data, and their sensitivity analysis about the inputs proved that it was not worth the big effort that was exerted to create a custom year weather file (Wasilowski and Reinhart 2009). 3.2.1. Ground Temperature Calculation and Basement Calibration Process Starting to calibrate the basement, the most important problem was to find the best curve of the ground temperature, which is located at the boundary between the ground and the soil. And it is coming more complicated because the basement was not a conditioned space. We could describe the center of the problem as follows: The building affects the ground temperatures beneath it, and the ground temperatures affect temperatures inside the building. The less insulated the basement is, the greater reciprocal affectation we get. In terms of simulations (if we are using DesignBuilder/EnergyPlus and Basement preprocessor), it means a para- dox; to calculate ground temperatures (Basement preprocessor), we need to know building internal temperatures, to calculate building internal temperatures (DesignBuilder/EnergyPlus) we should know ground temperatures. If we have a permanently conditioned building the problem is solved, as we already know reasonably building internal temperatures. However, the problem begins when we have a building that is conditioned just for certain periods and becomes significant when the building is not conditioned. We used an iterative approach that implies a series of iterations between packages: (Andolsun et al. 2011), (M. Staniec and Nowak 2011). 1. Run a first basement simulation using comfort conditioning temperatures as internal building temperatures. We used theoretical comfort temperatures for each month calculated with the neutrality temperature Tn (Eq. 1), which provides the center point for a comfort zone (Takkanon, 2006). Tn = 17.6 +(0.31xTav) (1) Where Tav is the mean outdoor temperature of the month. 2. Run a first DesignBuilder simulation using obtained ground temperatures. 3. Run a second Basement preprocessor simulation using monthly internal temperatures obtained within Design- Builder. 4. Run a second DesignBuilder simulation using previously obtained ground temperatures. 5. Run a third Basement preprocessor simulation using previously internal temperatures obtained within Design- Builder. After point 5, differences were very slight, but we continued until 5 iterations for each of the DesignBuilder and pg. 28 Kamel / Environmental Science and Sustainable Development, ESSD the Basement preprocessor. As shown in the chart, (Fig. 6). The most sensitive parameter for the basement’s calibration was the ground temperature. After reaching a reliable ground temperature as an input, we continued to simulate the basement model changing some other uncertain dif- ferent parameters until reaching a visually near-to-actual zone temperature. Accordingly, we chose the best curve after measuring the Normalized Mean Bias Error (NMBE), and the correla- tion coefficient compared with the real actual measurements by the sensors. 3.2.2. Inputs for the Basement Preprocessor Using ground temperatures with basements, the basement routine is used to calculate the face (surface) tempera- tures on the outside of the basement wall or the floor slab. The output of Basement preprocessor was the ground temperature, which was applied to the outer surface of every surface has a ground adjacency. (Fig. 7) shows the zone of the basement and its adjacencies conditions. The construction of the basement’s wall: cement/plaster 3cm. limestone 20cm. moisture insulation (bitumen) 2cm. and the soil, from inside to outside respectively, with a total thickness of 25cm. The construction of the basement’s slab: ceramic tiles 2cm., cement/mortar 2cm., sand 4 cm., moisture insulation (bitumen) 2cm., aerated concrete 15cm., and the soil, from inside to outside respectively, with a total thickness of 25cm. as shown in (Fig. 8). We tried to localize the inputs of the Basement preprocessor as much as possible as shown in Table 1, in order to reach (close to the real) ground temperature, as an output (EnergyPlus 2015). For the ground thermal effect on buildings, a key element are the thermal bridges, which will depend on the ratio of building area and building perimeter, we considered it under the (EquivSlab) object in the Table 1 below. This object provides the informa- tion needed to do the simulation as an equivalent square geometry by utilizing the area to perimeter ratio. This procedure was shown to be accurate by Cogil (Cogil, A. 1998; EnergyPlus 2015). However, we did not change all the inputs, some of them were kept as the defaults. Table 1. Localized inputs for the Basement preprocessor, for the Egyptian local building material properties Basement GHT.idd Object Category Input Source MatlProps Density (kg/m3) Density for Foundation Wall 1575 Calculated* Density for Floor Slab 2108 Calculated* Density for Soil 1960 Designbuilder, Alluvial clay 40% sand Density for Gravel 1840 Designbuilder, Gravel Specific Heat Capacity (J/Kg-K) Specific Heat for Foun- dation Wall 979 Calculated** Specific Heat for Floor Slab 951 Calculated** Specific Heat for Soil 840 Designbuilder, Alluvial clay 40% sand Specific Heat for Gravel 840 Designbuilder, Gravel Continued on next page pg. 29 Kamel / Environmental Science and Sustainable Development, ESSD Table 1 continued Basement GHT.idd Thermal Conductivity (W/m-K) Thermal Conductivity for Foundation Wall 0.63 Calculated*** Thermal Conductivity for Floor Slab 0.7 Calculated*** Thermal Conductivity for Soil 1.21 Designbuilder, Alluvial clay 40% sand Thermal Conductivity for Gravel 0.36 Designbuilder, Gravel Insulation R-Value (m2-K/W) R-value of any exterior insulation 0.01 Flag: Is the wall fully insulated? (FALSE) SurfaceProps ALBEDO Surface albedo for No snow conditions 0.3 For “Asphalt” (T.R. 2015) EPSLN Surface emissivity No Snow 0.95 For “Asphalt” (T.R. 2015) VEGHT (cm.) Surface roughness No snow conditions 0.032 For “Asphalt” BldgData DWALL (m.) basement wall thick- ness 0.25 The model DSLAB (m.) the thickness of the floor slab 0.25 The model ComBldg Every month’s av- erage air tempera- ture specifies the 12 monthly average basement temperatures (air temperature) (C) - First, calculated by the formula (Eq.1) us- ing Tav. For each month. - Then, the zone temp. output from Ener- gyPlus. EquivSlab APRatio (m.) the Area to Perimeter (A/P) ratio for the slab (63.9533/36.1396) =1.023 m. The model. EquivSizing Flag (FALSE) the dimensions will be input di- rectly AutoGrid SLABX (m.) X dimension of the building slab 7 The model SLABY (m.) Y dimension of the building slab 13.5 The model ConcAGHeight Height of the fndn wall above grade 0.0 SlabDepth (m) Thickness of the floor slab 0.25 The model BaseDepth (m) Depth of the basement wall below grade 2.4 The model * Density: Calculate the Mass of each layer. Then, Sum. of Masses and Sum. of Volumes, to calculate the Density of the assembly (Eq. 2). ** Specific Heat Capacity: A mass-weighted addition of the parts (Eq. 3). *** Thermal Conductivity: To obtain the R-value of each layer, according to its thickness, per unit area. Then, pg. 30 Kamel / Environmental Science and Sustainable Development, ESSD Figure 6. A flow chart describing the ground temperature and basement’s calibration process. pg. 31 Kamel / Environmental Science and Sustainable Development, ESSD Figure 7. The basement zone’s adjacencies conditions. Figure 8. Cross-section of the calibrated basement floor and slab layers Sum. of R. Finally, calculate the total Thermal conductivity according to the total Thickness and Sum. of R-values, (Eq. 4). To calculate the wall’s and slab’s thermal properties, we used the cross-section at (Fig. 8) and equations (Eq. 2 - 4). ρTotal = ∑(m) ∑(v) (2) ∑Cp = m1 ∑ m xcp1 + m2 ∑ m × cp2 + m3 ∑ m × cp3 +···... etc. (3) KTotal = ∑(L) ∑(R) (4) pg. 32 Kamel / Environmental Science and Sustainable Development, ESSD The inputs for The Site:GroundDomain:Basement, Xing approach was for the Al Minya city table 2, (Xing 2014). Table 2. Constant values for the Site:GroundDomain:Basement, Xing approach inputs (Xing 2014), p158. Region Country Station Latitude Longitude Ts, avg. Ts, amplitude,1 Ts, amplitude,2 PL1 PL2 1 EGY Al Minya 28.08 30.73 24.1 9.0 0.8 21 2 3.3. Inputs for the Simulated Model In Table 3., we mentioned only the customized inputs for the local buildings’ construction details of the calibrated model in Egypt. Other than these inputs, was kept as the default of the Designbuilder program. Table 3. Customized inputs for the building model calibration in Designbuilder Category Sub-category Item Input Activity Occupancy Density (People/m2) 0.15 Latent fraction 0.5 Metabolic rate Exercise Metabolic factor 1.0 Occupancy schedule From 15:00 to 22:00 Other gains Computers, load (w/m2) 300 Workday profile From 15:00 to 22:00 Miscellaneous (two ceiling fans), load (w/m2) 2*88= 176 General lighting, workday profile From 15:00 to 22:00 Environmental control Natural ventilation Natural ventilation set point (◦C) 24º Lighting, target illuminance (Lux) 300 Default display lighting density (w/m2) 20 Construction Walls Name Thickness (m.) No. of layers U-value External/Air. 0.25 4 2.08 External/ground.0.25 3, Fig. 8 1.771 Internal/Partitions.0.15 3 3.369 Roof/Floor/ Slab/Ceiling Flat roof. 0.2 5 2.695 Floor slab (Basement). 0.25 5, Fig. 8 1.767 Thermal mass Same as (In- ternal part.) 0.15 3 3.369 Doors External door. Metal door Airtightness Infiltration rate (ac/h). 0.5, very poor Openings Glazing Single clear (6 mm.), 1 layer, painted wooden window frame, U-value (w/m2.k) 5.778 Total Solar Transmission (SHGC) 0.819 Continued on next page pg. 33 Kamel / Environmental Science and Sustainable Development, ESSD Table 3 continued Category Sub-category Item Input Shading Window blinds type: Blind with medium re- flectivity slats. Position: Inside. Control type: Night outside low air temp. + day cooling. Lighting Fluorescent, compact (CFL), Normalized power density (w/m2-100Lux). 5.00 Luminaire type. Suspended HVAC Natural ventilation – No Heating/Cooling 3.4. The Model Hypotheses and Limitations – The model is a basement in a conventional reinforced concrete conventional building, which is the clear majority of this kind of buildings at Egypt. – The basement usage is a gym. The metabolism rate was taken into consideration during simulation. How- ever, for the proposed hypothetical residential usage, this would be different. – The calibrated model basement’s roof is a semi-exterior non-conditioned room. That was considered during the calibration process within setting the boundaries conditions. However, the proposed earth-sheltered building for application, should have a ground thick layer at the roof. – The research compared afterwards, a hypothetical earth-sheltered zone with the same corresponding conven- tional roof zone. In order to confirm the effect of ground-contact and show the effect of roof ground cover. This might not be a very accurate process because we did not calibrate the zone with ground cover on the roof before this comparison. 4. Results 4.1. Ground Temperature and Basement Calibration Comparisons The Iteration results between the (Basement preprocessor) and the (DesignBuilder/EnergyPlus) software shown in (Figs. 9, 10), are the output of the process described in the chart (Fig. 6). We changed some of the uncertainty inputs resulting in 15 different curves to reach the most near-to-actual curve, compared with the measured period. The most sensitive input was the ground temperature, which differed greatly when we changed to the Site:GroundDomain:Basement, Xing approach (EnergyPlus Development 2015). We chose the best-fit curves to go through the statistical analysis test as shown in (Fig. 11) for about three weeks in October. Calibration 11 inputs were the best to give very precise outputs as it showed high agreement, between the mea- sured and modeled data, with correlation of 98%, and errors with Mean Bias Error (MBE), Root Mean Square Error (RMSE) and Normalized Root Mean Square Error (NRMSE) of -1, 1.65 and 7.6%, respectively. 4.2. Thermal Comfort Analysis and Comparisons After the basement calibration, we conducted comparisons between two hypothetical living zones, after modifying the occupancy schedule of the basement from gym to the same living occupancy schedule of the roof, using the same calibrated roof inputs. This resulted in two very similar living zones, one on the roof level and the other one pg. 34 Kamel / Environmental Science and Sustainable Development, ESSD Figure 9. The basement zone’s adjacencies conditions. Figure 10. Cross-section of the calibrated basement floor and slab layers. Figure 11. The most visually typical sequence that is near-to-actual trials during the basement calibration process, using the ground temperature from the iterative approach, compared with the Site: GroundDomain: Basement, Xing approach on the underground level. We analyzed the thermal comfort using the Fanger model which is divided into the range of (+3: -3) of the Predicted Mean Vote (PMV). The ideal comfort sensation based on Fanger is (zero). We chose the Fanger analysis because this building was highly sealed, and the infiltration rate was very low, and the building was at the steady state condition (Attia and Carlucci 2015). The thermal comfort sensation in Egypt has a wider range and could be reached with a simple ceiling fan (Attia, Evrard, and Gratia 2012). The roof floor unconditioned living zone thermal comfort reached 5035 hrs. 57% of the year. However, the proposed perspective underground zone reached 8655 hrs. 99% of the year. With an increase by 58% of comfort hours. 5. Discussion Based on this research, we conclude that earth-sheltered buildings are the great passive solution for saving energy. The big dilemma related to this structural option is the difficulty inherent in simulating it precisely. In fact, the most sensitive input variables are the ground boundary temperature and the 3-D thermal bridging effect. pg. 35 Kamel / Environmental Science and Sustainable Development, ESSD Figure 12. Thermal comfort comparison between roof floor and underground floor of the same living zone, showing the stable thermal conditions with basements, compared with the conventional ones during 365 days. There are two methods for simulating 3-D thermal bridging effect and ground coupling using the EnergyPlus method; the first is Basement preprocessor through the GroundHeatTransfer:Basement object and the iterative approach which we introduced in detail in this paper, and the second is integrated Site:GroundDomain:Basement object. To distinguish which method is the most accurate, we compared both methods’ outputs with the actual zone measurements, given that we used the Xing inputs for the second approach. After the calibration process, we compared the thermal comfort of roof floor and underground floor living zones. Thermal comfort sensation depends on each country’s climate and people’s acceptance of extreme climate change differences. In Egypt, people tend to use ceiling or floor-length fans as their first choice to increase the thermal comfort zone. Their second choice is to use the AC, and only during a narrow range of the extremely hot weather months, to save energy. Consequently, we increased the PMV sensation range from zero to ± 2 levels, a range which may be reached easily by using a ceiling fan rather than an AC unit. Finally, this research did not examine basements for living purposes but examined basements to simulate them as a structural approach for an early design stage of earth-sheltered buildings in hot-arid climates, as a passive method for achieving thermal comfort. We did, however, conduct a different parallel research to measure people’s acceptance to live in earth-sheltered buildings (Heba Hassan et al. 2016; Ismail et al. 2013). 6. Conclusion In this research, we compared the results between two ground temperature calculation methods, in comparison with the actual measurement. Moreover, we provided a detailed simplified way to localize the inputs of the building materials’ thermal properties. The research demonstrated that the classic iterative way between EnergyPlus and the Basement preprocessor “GroundHeatTransfer:Basement” methods, to gain the ground boundary temperature, is more effective than the integrated “Site:GroundDomain:Basement” object, Xing approach. More specifically, the iterative approach and the precise local customized inputs displayed significantly high corre- lation curves compared with the actual measurements, with correlation results of 98%, and errors with Mean Bias Error (MBE), Root Mean Square Error (RMSE) and Normalized Root Mean Square Error (NRMSE) of -1, 1.65 and 7.6%, respectively. In addition, the Fanger model, using PMV, was used in this research to evaluate the underground level versus the roof level’s thermal comfort of the same living zone. More precisely, the earth-contact effect in the underground level increased the thermal comfort by 58% of Comfort hours, compared with the roof floor of the perspective zone. Finally, this research does not suggest that people should live underground, but rather that architects and structural engineers should introduce the innovative earth-contact effect for use in buildings as an implementation approach for the modern type of earth-sheltered building structures. pg. 36 Kamel / Environmental Science and Sustainable Development, ESSD 7. Acknowledgments The researcher would like to acknowledge the building owners for their gracious and kind help in the calibration process, by allowing us to place many sensors inside their apartments. A deep gratitude is for Inas El-Sabban for her sincere help in the English review. Furthermore, this research was funded under the RONPAKU program from the Japan Society for the Promotion of Science (JSPS), for Ph.D. studies. References 1. Al-Temeemi, A. A., & Harris, D. J. (2003). The Effect of Earth-Contact on Heat Transfer through a Wall in Kuwait. Energy and Buildings, 35, 399-404. Retrieved from 10.1016/S0378-7788(02)00114-7 2. Andolsun, S., Culp, C. H., Witte, M. J., & Haberl, J. (2011). EnergyPlus vs. DOE-2.1e: The Effect of Ground-Coupling on Energy Use of a Code House with Basement in a Hot-Humid Climate. Energy and Buildings, 43(7), 1663-1675. Retrieved from 10.1016/j.enbuild.2011.03.009 3. Anselm, A. J. (2008). Passive Annual Heat Storage Principles in Earth Sheltered Housing, a Supplementary Energy Saving System in Residential Housing. Energy and Buildings, 40, 1214-1219. Retrieved from 10.1016/j.enbuild.2007.11.002 4. Anselm, A. J. (2012). Earth shelters; a review of energy conservation properties in earth sheltered housing. In Energy Conservation. InTech. 5. Attia, S., & Carlucci, S. (2015). Impact of Different Thermal Comfort Models on Zero Energy Residential Buildings in Hot Climate. Energy and Buildings, 102(3), 117-28. 6. Attia, S., Evrard, A., & Gratia, E. (2012). Development of Benchmark Models for the Egyptian Residential Buildings Sector. Applied Energy, 94(2012), 270-284. Retrieved from 10.1016/j.apenergy.2012.01.065 7. Auxiliary Programs EnergyPlus Documentation. (Vol. 2).(2015).Retrieved from http://nrel.github.io/Energ yPlus/AuxiliaryPrograms/AuxiliaryPrograms/ 8. Carmody, J., & Sterling, R. (1985). Earth Sheltered Housing Design. In R. Sterling (Ed.), . Minnesota: Van Nostrand Reinhold. Cogil, C. A. (1998). Modeling of Basement Heat Transfer and Parametric Study of Basement Insulation for Low Energy Housing. Pennsylvania State University. 9. Derradji, M., & Aiche, M. (2014). Modeling the Soil Surface Temperature for Natural Cooling of Buildings in Hot Climates. Procedia Computer Science, 32, 615-621. Retrieved from 10.1016/j.procs.2014.05.468 10. El-Din, M. M. S. (1999). On the Heat Flow into the Ground. Renewable Energy, 18(4), 473-490. Retrieved from 10.1016/ S0960-1481(99)00005-1;http://dx.doi.org/10.1016/S0960-1481 11. EnergyPlus Input Output Reference: The Encyclopedic Reference to EnergyPlus Input and Output (Vol. 2488). (2015). Freney, M., Soebarto, V., & Williamson, T. (2012). Learning from ‘ Earthship ’ Based on Monitoring and Thermal Simulation. In 6th Annual Conference of the Architectural Science Association (ANZAScA). Griffith University. 12. Hassan, H., Arima, T., Ahmed, A., Sumiyoshi, D., & Akashi, Y. (2014). Testing the Basements Thermal Performance as an Approach to the Earth-Sheltered Buildings Application at Hot Climates, Case Study (Egypt). In ASim2014 Proceedings (p. 507-514). Nagoya, Japan: IBPSA-Asia ASim-Japan. 13. Hassan, H., & Sumiyoshi, D. (2017). Earth-Sheltered Buildings in Hot-Arid Climates: Design Guidelines. Beni-Suef University Journal of Basic and Applied Sciences. Retrieved from http://linkinghub.elsevier.com /retrieve/ pii/S2314853516301585 pg. 37 Kamel / Environmental Science and Sustainable Development, ESSD 14. Heba, H. A. (2012). The Possibility of Applying the Earth-Sheltered Building Type for Housing Projects be- tween Humid and Dry Climates Case Study Egypt and Japan. In International society of habitat engineering and design conference, ISHED (Vol. 8). Shanghai, China: Tongji University. 15. Ip, K., & Miller, A. (2009). Thermal Behaviour of an Earth-Sheltered Autonomous Building – The Brighton Earthship. Renewable Energy, 34(9), 2037-2043. Retrieved from 10.1016/j.renene.2009.02.006 16. Ismail, H., Arima, T., Ahmed, A., & Akashi, Y. (2013). Measuring the Possibility of Living in the Earth- Sheltered Building Type between Egypt and Japan. In Building Simulation Cairo 2013 Towards Sustainable & Green Life, ed. Dr. Mohammad Fahmy BPSA-Egypt (Vol. 8, p. 430-441). Cairo, Egypt: AGD Publishing Cairo IBPSA-Egypt. 17. Janssen, H., Carmeliet, J., & Hens, H. (2004). The Influence of Soil Moisture Transfer on Building Heat Loss via the Ground. Building and Environment, 39(7), 825-836. Retrieved from 10.1016/j.buildenv.2004.01.004 18. Kharrufa, S. N. (2008). Evaluation of Basement’s Thermal Performance in Iraq for Summer Use. Journal of Asian Architecture and Building Engineering, 7(2), 411-417. 19. Kruis, N., & Krarti, M. (2016). Three-Dimensional Accuracy with Two-Dimensional Computation Speed: Using the KivaTM Numerical Framework to Improve Foundation Heat Transfer Calculations. Journal of Building Performance Simulation, 1493, 1-22. Retrieved from http://www.tandfonline.com/doi/full/10.108 0/ 19401493.2016.1211177. 20. Kumar, R., Sachdeva, S., & undefined S.C. Kaushik. (2007). Dynamic Earth-Contact Building: A Sustain- able Low-Energy Technology. Building and Environment, 42(6), 2450-2460. Retrieved from 10.1016/j.buildenv.2006.05.002. 21. Lazzarin, R. M., Castellotti, F., & Busato, F. (2005). Experimental Measurements and Numerical Modelling of a Green Roof. Energy and Buildings, 37(12), 1260-1267. Retrieved from 10.1016/j.enbuild.2005.02.001 22. Oke, T. R. (2015). Statewide Agricultural Land Use Baseline. In Boundary Layer Climates. Vancouver: Taylor & Francis e-Library. 23. RhManager User Manual For Version 2.10. (2010). 24. Serageldin, A. A., Abdelrahman, A. K., Ali, A. H., Ali, S., O., M. R., & Ookawara. (2015). Soil Temperature Profile for Some New Cities in Egypt : Experimental Results and Mathematical Model. In 14th international conference on sustainable energy technologies – set 2015 (p. 1-9). Nottingham, UK: SET. 25. Staniec, M., & Nowak, H. (2011). Analysis of the Earth-Sheltered Buildings’ Heating and Cooling En- ergy Demand Depending on Type of Soil. Archives of Civil and Mechanical Engineering, 11(1), 221-235. Retrieved from 10.1016/S1644-9665(12)60185-X 26. Staniec, M., & Nowak, H. (2016). The Application of Energy Balance at the Bare Soil Surface to Predict An- nual Soil Temperature Distribution. Energy and Buildings, 127, 56-65. Retrieved from 10.1016/j.enbuild.2016.05.047 27. Szabó, J., & Kajtá, L. (2016). Expected Thermal Comfort in Underground Spaces. Retrieved from http://w ww.epget.bme.hu/docs/Kutatas/Konferencia/expres2016/15 J Szabo,L Kajtar EXPRES 2016.pdf 28. Takkanon, P. (2006). Design Guidelines for Thermal Comfort in Row Houses in Bangkok. In The 23rd conference on passive and low energy architecture (p. 6-8). Geneva, Switzerland. 29. Wasilowski, H., & Reinhart, C. (2009). Modelling an Existing Building In Design builder / E + : Custom Versus Default Inputs. In Building simulation 2009. Glasgow. 30. Xing, L. U. (2014). Estimations of Undisturbed Ground Temperatures using Numerical and Analytical Modeling, Phd. Oklahoma State University. pg. 38 Introduction Climate Analysis of the selected city in Egypt Method Measurements Weather File Ground Temperature Calculation and Basement Calibration Process Inputs for the Basement Preprocessor Inputs for the Simulated Model The Model Hypotheses and Limitations Results Ground Temperature and Basement Calibration Comparisons Thermal Comfort Analysis and Comparisons Discussion Conclusion Acknowledgments