Available online at www.HighTechJournal.org HighTech and Innovation Journal Vol. 2, No. 2, June, 2021 87 Thermodynamic Analysis of a Combined Single Effect Vapour Absorption System and tc-CO2 Compression Refrigeration System Abhishek Verma a, S. C. Kaushik a , S. K. Tyagi a* a Centre for Energy Studies, Indian Institute of Technology Delhi, Hauz Khas, New Delhi-110016, India. Received 22 September 2020; Revised 14 March 2021; Accepted 16 April 2021; Published 01 June 2021 Abstract The transcritical CO2 refrigeration system is coupled with the single effect vapour absorption with LiBr-water as a working pair, having the objective of enhancing the performance of the low temperature transcritical refrigeration system while using a natural working pair and reducing the electricity consumption to produce low temperature refrigeration. The high grade waste heat rejected in the gas cooler of the tc-CO2 compression refrigeration system (TCRS) is utilized to run the single effect vapour absorption system (SEVAR) to enhance the energy efficiency of the system. The gas cooler in the transcritical CO2 system has heat energy at a high temperature and pressure, which is utilized to run the vapour absorption system, while the other refrigerant heat exchanger provides subcooling to further enhance the performance. The combined cycle can provide refrigeration temperature at different levels, to use it for different applications. Energetic and exergetic analysis have been done to analyze the combined system to compute the performance parameters and the irreversibilities occurring in different components to further increase the performance. The combined system is optimized for various heat rejection and refrigeration temperatures. The COP of the combined system has been enhanced by 24.88% while the enhancement in exergetic efficiency (ηex) is observed at 10.14%, respectively, over tradition transcritical CO2 compression refrigeration system, with -10°C as an evaporation (TCRS cooling) temperature and the exit temperature of gas cooler T4 being 40°C. Keywords: Exergy; Vapour Absorption; Carbon Dioxide; Waste Heat; Transcritical. 1. Introduction Refrigeration and air conditioning play a vital role in almost every sector of society. Global warming and the depletion of the ozone layer have become the key issues for conventional refrigeration systems. In 1987, the Montreal Protocol [1] set a time limit for the usage of chlorofluorocarbon (CFC) and hydrochlorofluorocarbon (HCFC) refrigerants, as they are responsible for ozone depletion, but the use of hydroflourocarbons (HFC)s was being the major concern as its effects are hazardous for the environment and climate change. In 1997, the Kyoto Protocol [2] limited the use of HFCs with large GWP. In 1998, Robinson and Groll [3] suggested the use of naturally occurring refrigerants, which do have a low GWP and environment friendly. CO2 as a naturally occurring refrigerant having good thermophysical properties [4] finds favour across almost all sectors of refrigeration to be used as the refrigerant [5]. It has a critical temperature of 30.85°C [3]. Transcritical CO2 (R744) has been adopted worldwide for supermarkets, food storage, industrial applications, etc., even in locations having high ambient temperatures [6]. In CO2 refrigeration systems, subcooling plays an important role in upgrading the performance of the system. Dedicated subcooling methods improve COP by 30%, thermoelectric systems by 25.6%, internal heat exchangers improve COP by 12 while 22% with economizers [7]. In a CO2 refrigeration system, Bellos and Tzivanidis [8] reported that the performance of the system upto 75% by the use of a mechanical subcooling system over the basic configuration. Use * Corresponding author: tyagisk@ces.iitd.ac.in; sudhirtyagi@yahoo.com http://dx.doi.org/10.28991/HIJ-2021-02-02-02  This is an open access article under the CC-BY license (https://creativecommons.org/licenses/by/4.0/). © Authors retain all copyrights. mailto:tyagisk@ces.iitd.ac.in mailto:sudhirtyagi@yahoo.com https://creativecommons.org/licenses/by/4.0/ https://orcid.org/0000-0001-5879-186X https://orcid.org/0000-0002-3103-7100 HighTech and Innovation Journal Vol. 2, No. 2, June, 2021 88 of ejector and thermoelectric subcooling enhance the performance upto 40% [9]. Internal heat exchangers for subcooling improve the COP by 12 and 25% by using thermoelectric subcooling for specific operating conditions [10]. Mohammadi [11] studied various configurations of the CO2 refrigeration system coupled with different absorption chillers to produce refrigeration at different temperature levels from -80°C to -30°C with an increase of COP upto 200% in a few cases. The mean COP improvement for CO2 refrigeration systems has been reported to be 23% with subcooling by absorption chillers [12]. The net impact of GWP is 1 for CO2 refrigeration systems [13]. Basso et al. [14] integrated the transcritical CO2 heat pump to reduce the load of the external heat source for a hybrid system using dynamic simulation. The working pair used in the absorption refrigeration system is ecofriendly, non-flammable, and non-toxic in nature, having low operating pressures [15]. Presently, the emphasis is on energy-efficient systems to fulfill the demand for refrigeration and air conditioning (RAC) in society. To improve the energy efficiency of the system, exergy analysis is the preferred tool to be used as it is defined as the potential of a stream to cause change, as well as it tells the quality of the system as an effective portion of the potential of the system to have an impact on the environment [16, 17]. It also quantifies the irreversibilities occurring in components of the system. The reported literature review suggests that subcooling the tc-CO2 system has been showing promising enhancement in the performance of the system. Thus, coupling the absorption system with the tc-CO2 system improves the overall system performance and provides refrigeration with different temperature levels. The present study focuses on the use of waste heat to run the single effect vapour absorption system (SEVAR). The waste heat being rejected in the gas cooler (GC) of the tc-CO2 compression refrigeration system (TCRS) [18] is being utilized to run SEVARS, which improves the energy efficiency of the combined system. The exergy analysis and parametric study of the combined system are being presented. 2. System Description The SEVARS are coupled with TCRS. The superheated refrigerant (CO2) is compressed in a compact compressor to a high temperature and pressure. The heat rejection of high pressure and temperature CO2 that occurred in gas cooler 1 (GC1) and gas cooler 2 (GC2) is utilized by circulating the water. In GC1, water at 1 atmospheric pressure and 100°C enters and changes its phase from liquid water to saturated steam at constant temperature of 100°C, as the temperature of CO2 is well above 100°C. The generated saturated steam is utilized as the heat input to the SEVARS, where the generator is kept at 90°C [10]. The temperature of the refrigerant (CO2) is still higher (more than 100°C) after rejecting heat in GC1, so it is required to further reject heat in GC2 to an optimum gas cooler temperature of 40°C, by circulating the water at 25°C at 1 atm pressure. The hot water obtained from GC2 can be utilized for various applications, such as desalination, distillation, industrial and domestic uses [17]. Figure 1. TCRS coupled with SEVARS HighTech and Innovation Journal Vol. 2, No. 2, June, 2021 89 Further the refrigerant is passed through refrigerant heat exchanger (RHXTC), to improve the efficiency of TCRS and expanded through the refrigerant throttling valve RTVTC. The refrigerant CO2 is expanded upto a low temperature of - 10°C. The saturated refrigerant vapour at the exodus of evaporator gets superheated vapour while exchanging heat in RHXTC which reduces the compressor work considerably. The working of SEVAR Libr-H2O based system has reported by various authors [19-23]. 3. Thermodynamic Analysis 3.1. System Model The analysis of the combined cycle includes mass balance, concentration balance, energy balance and exergy balance for individual component and is presented as [16, 22]: ∑ �̇�𝑖 − ∑ �̇�𝑒 = 0 (1) ∑ �̇�𝑖 �̇�𝑖 − ∑ �̇�𝑒 �̇�𝑒 = 0 (2) ∑ �̇� − ∑ �̇� = ∑ �̇�𝑒 ℎ̇𝑒 − ∑ �̇�𝑖 ℎ̇𝑖 (3) Form 1st law of thermodynamics (FLT), the (COP) of TCRS is given as: 𝐶𝑂𝑃𝑇𝐶 = �̇�𝐸𝑡𝑐. �̇�𝐶 (4) Form 1st law of thermodynamics (FLT), the (COP) of VARS is given as: 𝐶𝑂𝑃𝑉𝐴 = �̇�𝐸𝑣𝑎. �̇�𝐺 + �̇�𝑃 (5) Form 1st law of thermodynamics (FLT), the (COP) of combined is given as: 𝐶𝑂𝑃𝑁𝐸𝑇 = �̇�𝐸𝑡𝑐. + �̇�𝐸𝑣𝑎. �̇�𝐶 (6) Exergy flow rate for a stream on each state is defined as: �̇� = �̇�[(ℎ − ℎ0) − 𝑇0(𝑠 − 𝑠0)] (7) Considering a steady state process, the exergy destruction rate (𝐸�̇�) to a component is specified as [16, 24]: 𝐸�̇� = ∑ �̇�𝑖 − ∑ �̇�𝑒 + ∑ �̇� (1 − 𝑇0 𝑇 ) − ∑ �̇� (8) Based on 2nd law of thermodynamics (SLT), the performance parameter (exergetic efficiency) for the system given as [16, 24]: 𝜂𝑒𝑥𝑇𝐶 = �̇�𝐸𝑡𝑐. |1 − 𝑇0 𝑇𝑟𝑡𝑐 | �̇�𝐶 (9) 𝜂𝑒𝑥𝑉𝐴 = �̇�𝐸𝑣𝑎. |1 − 𝑇0 𝑇𝑟𝑣𝑎 | �̇�𝐺. |1 − 𝑇0 𝑇𝐺 | + �̇�𝑃 (10) 𝜂𝑒𝑥𝑁𝐸𝑇 = (�̇�𝐸𝑡𝑐. |1 − 𝑇0 𝑇𝑟𝑡𝑐 | + �̇�𝐸𝑣𝑎. |1 − 𝑇0 𝑇𝑟𝑣𝑎 |) �̇�𝐶 + �̇�𝑃 (11) 3.2. Assumptions The following have been made to analyze the combined system:  Entirely, individual components of the combined system are considered as control volume.  The combined system follows steady state conditions.  The pressure drop in connecting lines and components is neglected. HighTech and Innovation Journal Vol. 2, No. 2, June, 2021 90  The temperature of the refrigerated space required is supposed to be 5°C higher to the respective evaporator temperature.  The refrigerant (water) leaving condenser of SEVAR is considered to be saturated liquid.  The exodus of evaporator is considered to be saturated vapour.  Pumping in SEVAR is considered to be iscentropic [19].  Entropy change through the solution throttling valve (STV) is derelicted and the temperature is expected to be constant [19].  The SEVARS is well away from crystallization.  Water at 25°C, 1 atm is used to cool the GC2 TCRS and condenser & absorber of SEVARS. 3.3. Research Methodology The research methodology has been explained in the flowchart for the combined analysis of the coupled cycle. Figure 2. Flowchart for the analysis of the combined cycle End Input & Assumptions: TETC, T4, T10, T11, T8, Ɛgc1, Ɛgc1, Ɛrhx1, mco2, P0, T0, TG, TA, TC, TE, ƐSHEX, T22, T24 Specifications of state equations: P= Psat (T), H=H(T,X), X=X(P,T) mCO2 = m1 = m2 = m3 = m4 = m5 = m6 = m7 Patm = P8 = P9 = P10 = P22 = P23 = P24 PETC = P1 = P6 = P7 ; PGC = P2 = P3 = P4 = P5 PETC = Psat (TETC) ; PE = Psat (TE) ; PC = Psat (TC) TA = T12, TG = T15 = T18, TC = T19, TE = T20 = T21 PE = P20 = P21 = P12 ; PC = P13 = P14 = P15 = P16 = P18 = P19 Calc. h7, s7, h8, s8, h10, s10, h11, s11 T1 from Ɛrhx1, calc. h1, s1, PGC From mass and material balance: Xs=X(TA, PE) ; Xw=X(TG, PC) ms = mw + mr ; ms* Xs = mw* Xw ; ms = m12 = m13 = m14 ; mw = m15 = m16 = m17 ; mr = m19 = m20 = m21 ; Xs = X12 = X13 = X14 ; Xw = X15 = X16 = X17 ; X = X = X = X = X = 0 Calc. specific enthalpies, specific entropies, temperature and pressure, etc., at all state points using state points equation Calc. s13, h17 = h16, T17, s16, s17, T14, s14, etc. Calc. mass flow rate from water steam loop for VARS. Using energy balance calc QA, QC, QE, QETC, QG = QGC1, QGC2, WC, Calc. exergy flow for each state points. Calc. performance parameters using useful equations COPTCRS COPVARS COPNET , ηextcrs ;ηexvars ;ηexNet Start HighTech and Innovation Journal Vol. 2, No. 2, June, 2021 91 3.4. Input parameters  Isentropic efficiency of compressor is [3]: 𝜂𝑐 = 0.815 + 0.022𝑟𝑝 − 0.0041(𝑟𝑝) 2 + 0.0001(𝑟𝑝) 3 (12)  Generator temperature, (Tg) = 90°C;  Evaporator temperature in SEVARS, Teva = 7°C;  Mass flow rate of refrigerant (CO2) in TCRS, mrtc = 1 kg/s;  Effectiveness of gas cooler 1, (εgc1)= 0.8;  Effectiveness of gas cooler 2, (εgc2)= 0.8;  Effectiveness of solution heat exchanger (SHX), εshx = 0.7;  Condenser and absorber temperatures, Tcond = Ta = 35°C. 4. Results and Discussion 4.1. Simulation Validation The validation of the combined system, has been done by validating the two cycles separately as there is no literature available for this coupled cycle in this manner. The analysis of single effect VARS cycle is compared with the results presented by Kaushik and Arora [20]. The input parameters considered for the validation of cycle are: TE=7.2°C, TG=87.8°C, TA = TC = 37.8 °C, solution heat exchanger effectiveness = 0.7, refrigerant mass flow rate = 1 kg/s. Table. Shows the comparison of the results obtained by the Kaushik and Arora [20] and the present study for energy transfer involved in various components and the COP of the system. It is seen that the there is a good agreement among the results obtained in the present study and those available in the literature. Also, Figures 3 and 4 show that the variation of COP with generator temperature ant various absorber temperature shows similar trends for the present study and those reported in the literature. Thus, the present validation of the system is reliable. Table 1. Energy analysis comparison of present work with numerical values given in Kaushik & Arora [20] for SEVARS Input Data : TE=7.2°C, TG=87.8°C, TA = TC = 37.8 °C, solution heat exchanger effectiveness = 0.7, refrigerant mass flow rate = 1 kg/s S. No. Component Kaushik & Arora [20] Present study Difference Q (kW) Q (kW) (%) 1. Generator 3095.7 3096 -0.00969 2. Absorber 2945.27 2946 -0.02479 3. Condenser 2505.91 2506 -0.00359 4. Evaporator 2355.45 2355 0.019105 5. Solution Heat Exchanger 518.72 519.5 -0.15037 6. Solution throttle valve 0 0 _ 7. Refrigerant throttle valve 0 0 _ 8. Pump 0.0314 0.03093 1.496815 9. Energy Input 5451 5451 0 10. COP (No Dimensions) 0.7609 0.7608 - Figure 3. COP variation with generator temperature in single effect systems, (Kaushik and Arora [20]) Figure 4. COP variation with generator temperature in single effect systems (Present study) 55 65 75 85 95 105 115 125 135 145 155 165 175 0.15 0.35 0.55 0.75 0.95 1.15 1.35 1.55 TG(°C) C O P V A R S TA=30°CTA=30°C TA=35°CTA=35°C TA=37.8°CTA=37.8°C TA=40°CTA=40°C HighTech and Innovation Journal Vol. 2, No. 2, June, 2021 92 4.2. COP and Exergetic Efficiency The trend of COP with gas cooler pressure PGC and exergetic efficiency (ηex) with PGC is shown in Figure 5, having GC2 outlet temperature to be 40°C. The COP and exergetic efficiency (ηex) of the system increases as the PGC increases upto an optimum gas cooler pressure and then started decreasing gradually. At constant gas cooler outlet temperature, the PGC increases the refrigerating capacity and the compressor work, while initially the rate of increase in refrigerating effect is more hence the exergetic efficiency (ηex) and COP and increases upto an optimum PGC and further decreases gradually beyond this optimum PGC as shown in Table 2. For an evaporation (cooling) temperature of -10°C, in TCRS, outlet temperature of gas cooler T4 being 40°C, the optimum PGC is found to be approx. 10 MPa. The thermodynamic state points, energy transfer, exergy destruction are computed in Tables 5-7. The performance parameters of the combined system is compared with the base case of TCRS and accessible in Table 6. Figure 5. Influence of PGC on COP and ηex of TCRS Table 2. The deviation of power input (W), refrigerating effect (QEtc), COP & exergetic efficiency (ηex) of TCRS with pressure of gas cooler for (T4= 40°C) and (TEtc = -10°C) PGC (MPa) W (kW) QEtc (kW) COPTCRS ηexTCRS 8.0 72.72 81.46 1.12 12.53 8.2 74.56 89.89 1.206 13.49 8.4 76.36 99.97 1.309 14.65 8.6 78.14 112.2 1.436 16.07 8.8 79.89 126.7 1.586 17.74 9.0 81.61 140.6 1.723 19.27 9.2 83.3 151.1 1.814 20.3 9.4 84.98 158.5 1.866 20.87 9.6 86.63 163.9 1.892 21.17 9.8 88.26 168 1.903 21.3 10.0 89.87 171.3 1.906 21.33 10.2 91.46 174.1 1.903 21.29 10.4 93.04 176.4 1.896 21.22 10.6 94.59 178.5 1.887 21.11 10.8 96.14 180.3 1.876 20.99 11.0 97.66 182 1.863 20.85 11.2 99.18 183.5 1.85 20.7 11.4 100.7 184.8 1.836 20.54 11.6 102.2 186.1 1.821 20.38 11.8 103.6 187.2 1.807 20.21 12.0 105.1 188.3 1.792 20.04 7000 8000 9000 10000 11000 12000 13000 1 1.2 1.4 1.6 1.8 2 10 12 14 16 18 20 22 24 PGC (Kpa) C O P T C R S COPTCRSCOPTCRS h e x ,T C R S (% ) hex,TCRShex,TCRS HighTech and Innovation Journal Vol. 2, No. 2, June, 2021 93 Table 3. State points obtained by thermodynamic analysis State T (°C) s (kJ/kgK) h (kJ/kg) x m (kg/s) P (kPa) 1. 30 -0.6658 -22.42 - 1 2649 2. 151.9 -0.6325 67.48 - 1 10004 3. 110.4 -0.7685 12.61 - 1 10004 4. 40 -1.383 -193.8 - 1 10004 5. 27.51 -1.543 -243 - 1 10004 6. -10 -1.492 -243 - 1 2649 7. -10 -0.8405 -71.64 - 1 2649 8. 25 0.3669 104.8 - 0.7217 101.3 9. 93.3 1.231 390.8 - 0.7217 101.3 10. 100 1.307 419.1 - 0.02432 101.3 11. 100 7.354 2676 - 0.02432 101.3 12. 35 0.2184 81.15 0.5408 0.1091 1.002 13. 35 0.2184 81.16 0.5408 0.1091 5.627 14. 62.29 0.3945 137.7 0.5408 0.1091 5.627 15. 90 0.4751 239.6 0.6477 0.09108 5.627 16. 51.93 0.2775 171.9 0.6477 0.09108 5.627 17. 51.93 0.2775 171.9 0.6477 0.09108 1.002 18. 90 8.662 2669 0 0.01802 5.627 19. 35 0.505 146.6 0 0.01802 5.627 20. 7 0.5246 146.6 0 0.01802 1.002 21. 7 8.973 2513 0 0.01802 1.002 22. 25 0.3669 104.8 - 1 101.3 23. 37.45 0.5381 156.9 - 1 101.3 24. 25 0.3669 104.8 - 1 101.3 25. 35.86 0.5166 150.3 - 1 101.3 Table 4. Energy transfer in various components Component Q (kW) W (kW) TCRS Evaporator 171.4 - Compressor - 134.7 Gas Cooler (GC1) 54.87 - Gas Cooler (GC2) 206.4 - RHX 54.9 - VARS Evaporator 42.64 - Condenser 45.43 - Absorber 52.08 - Generator 54.87 - HighTech and Innovation Journal Vol. 2, No. 2, June, 2021 94 Table 5. Exergy destructed rate in various components Component Exergy destructed (kW) TCRS Compressor 9.906 Evaporator 3.621 Gas Cooler (GC1) 3.293 Gas Cooler (GC2) 2.65 RHX 4.38 RTVTC 15.28 TotalTCRS 39.13 VARS Evaporator 0.80 Condenser 0.81 Absorber 2.39 Generator 2.75 SHX 0.36 STV 0.01 RTVVA 0.12 TotalVARS 7.219 Net Exergy Destruction 46.35 Table 6. Performance parameters (COP and ηex) comparison with the base TCRS TCRS SEVARS Combined system % increase COP 1.91 0.78 2.38 24.88 ηex (%) 21.33 17.62 23.49 10.14 4.3. Exergy Destruction Figure 6 presents the exergy destruction in various components of TCRS & SEVARS. It is found that the exergy destruction in SEVAR is maximum in generator followed by absorber and condenser, while the exergy destruction in TCRS is maximum in RTVTC followed by compressor, RHX, evaporator, GC1 and GC2 respectively. The exergy destruction of the components implies us to use the components with higher energy efficiency. Therefore to improve the performance of SEVARS, the design of generator & absorber should be focused. In TCRS, the energy can be recovered by replacing the throttling valve with other expansion devices such as expander, ejector, work recovery turbine etc. to further progress the performance of the combined system. Figure 6. Exergy destructed in various components 0 5 10 15 20 25 30 35 % E x er g y D es tr u ct io n Components HighTech and Innovation Journal Vol. 2, No. 2, June, 2021 95 4.4. Gas Cooler Pressure Figure 7 presents the variation of PGC with TCRS evaporation temperature TETC with different outlet temperature of gas cooler. The PGC is an important parameter in tc- CO2 compression refrigeration system. The PGC depends upon the exit temperature of gas cooler and the temperature of evaporator [17]. The PGC declines as the evaporator temperature increases, while it increases as the outlet temperature of gas cooler (T4) increases. The gas cooler pressure is the deciding factor in sizing the components of the transcritical refrigeration system and has an influence on the COP of the system. To maximize the performance parameters of TCRS, the optimum PGC is approximated to be 10 MPa for an evaporator temperature at -10°C and outlet temperature of gas cooler (T4) being 40°C. Figure 7. Influence of evaporator temperature of TCRS on PGC at different T4 4.5. COP vs Evaporator Temperature Figure 8 presents the trend of COPTCRS and COPNET (combined system) with temperature of evaporator. Both the COP trends increases with the increase in evaporating temperature. This is due to the fact, as the temperature of evaporator increases, the work of compressor decreases and hence the COP. The utilization of waste heat from the gas cooler has increased the cooling capacity of TCRS, also provides additional cooling capacity is observed through SEVARS. Figure 8. Influence of evaporator temperature of TCRS on COP at different T4 -25 -20 -15 -10 -5 0 5 8000 9000 10000 11000 12000 TEtc (°C) P G C PGCT[4]=35(°C)PGCT[4]=35(°C) PGCT[4]=40(°C)PGCT[4]=40(°C) PGC T[4]=45(°C)PGC T[4]=45(°C) -25 -20 -15 -10 -5 0 5 1 1.5 2 2.5 3 3.5 TEtc (°C) C O P COPTCRST[4]=35(°C)COPTCRST[4]=35(°C) COPTCRST[4]=40(°C)COPTCRST[4]=40(°C) COPTCRST[4]=45(°C)COPTCRST[4]=45(°C) COPNetT[4]=35(°C)COPNetT[4]=35(°C) COPNetT[4]=40(°C)COPNetT[4]=40(°C) COPNetT[4]=45(°C)COPNetT[4]=45(°C) HighTech and Innovation Journal Vol. 2, No. 2, June, 2021 96 4.6. Exergetic Efficiency (ηex) vs. Evaporating Temperature Figure 9 presents the trends of exergetic efficiency (ηex) of TCRS and the combined system with the TCRS evaporating temperature with changed gas cooler outlet temperature.It is observed that the refrigerating temperature has a dominant effect on the exergetic efficiency of the combined system. Both the exergetic efficiencies gets the optimum peak and decreases gradually with the increase in evaporating temperature, as the maximum work potential to brought to the system to the environmental conditions decreases as the temperature of evaporator increases and hence the exergetic efficiency. Figure 9. Influence of evaporator temperature of TCRS on (ηex) at different T4 5. Conclusions The following conclusions have been drawn from the results:  Coupling the two cycles increases the COP of the system interestingly. The COP of the combined system increases by 24.88% while the exergetic efficiency is increased by 10.14% over the modified TCRS having RHXTC.  There is an optimum gas cooler pressure for an evaporator temperature and a gas cooler outlet temperature of T4 for TCRS. PGC is found to be 10 MPa at an evaporation temperature of -10°C and a T4 temperature of 40°C.  The COP of the system increases as the evaporation temperature increases. On the contrary, it decreases with the rise in outlet temperature of the gas cooler.  The exergetic efficiency shows a peak with the evaporation temperature, which further decreases with the increase in the evaporation temperature. However, it increases with T4.  Efficient compressors and heat exchangers would result in an increase in the performance of the combined system.  The exergy destructed in RTVTC is considerably high; therefore, replacement of the throttling (expansion) valve by an expander, ejector, and work-recovery turbine will contribute to an increase in the performance of the system. 6. Declarations 6.1. Author Contributions A.V.: Conceptualization, Writing - Original Draft preparation, Formal analysis, Methodology; S.K.T.: Formal analysis, Writing- Reviewing and Editing, Supervision; S.C.K.: Conceptualization, Reviewing and Editing, Supervision. 6.2. Data Availability Statement The data presented in this study are available in article. -25 -20 -15 -10 -5 0 5 10 15 20 25 30 TEtc (°C) h e x hex,TCRST[4]=35(°C)hex,TCRST[4]=35(°C) hex,TCRST[4]=40(°C)hex,TCRST[4]=40(°C) hex,TCRST[4]=45(°C)hex,TCRST[4]=45(°C) hex,NetT[4]=35(°C)hex,NetT[4]=35(°C) hex,NetT[4]=40(°C)hex,NetT[4]=40(°C) hex,NetT[4]=45(°C)hex,NetT[4]=45(°C) HighTech and Innovation Journal Vol. 2, No. 2, June, 2021 97 6.3. Funding and Acknowledgements The support of Ministry of Education (MOE), and Ministry of New and Renewable Energy (MNRE), Government of India is duly acknowledged. 6.4. Declaration of Competing Interest The authors declare that they have no known competing financial interests or personal relationships that could have appeared to influence the work reported in this paper. 7. References [1] Medical and Chemicals Technical Options Committee. (1987). Montreal protocol on substances that deplete the ozone layer. Washington, DC, US Government Printing Office, 26, 128-136. [2] Fartaj, A., Ting, D. S.-K., & Yang, W. W. (2004). Second law analysis of the transcritical CO2 refrigeration cycle. Energy Conversion and Management, 45(13-14), 2269–2281. doi:10.1016/j.enconman.2003.07.001. [3] Robinson, D. M., & Groll, E. A. (1998). Efficiencies of transcritical CO2 cycles with and without an expansion turbine: Efficiency of transcritical CO2 cycles with and without an expansion turbine. International Journal of Refrigeration, 21(7), 577– 589. doi:10.1016/s0140-7007(98)00024-3. [4] Ma, Y., Liu, Z., & Tian, H. (2013). A review of transcritical carbon dioxide heat pump and refrigeration cycles. Energy, 55, 156–172. doi:10.1016/j.energy.2013.03.030. [5] Pearson, A. (2005). Carbon dioxide—new uses for an old refrigerant. International Journal of Refrigeration, 28(8), 1140–1148. doi:10.1016/j.ijrefrig.2005.09.005. [6] Gullo, P., Hafner, A., & Banasiak, K. (2018). Transcritical R744 refrigeration systems for supermarket applications: Current status and future perspectives. International Journal of Refrigeration, 93, 269–310. doi:10.1016/j.ijrefrig.2018.07.001. [7] Llopis, R., Nebot-Andrés, L., Sánchez, D., Catalán-Gil, J., & Cabello, R. (2018). Subcooling methods for CO2 refrigeration cycles: A review. International Journal of Refrigeration, 93, 85–107. doi:10.1016/j.ijrefrig.2018.06.010. [8] Bellos, E., & Tzivanidis, C. (2019). CO2 Transcritical Refrigeration Cycle with Dedicated Subcooling: Mechanical Compression vs. Absorption Chiller. Applied Sciences, 9(8), 1605. doi:10.3390/app9081605. [9] Liu, X., Fu, R., Wang, Z., Lin, L., Sun, Z., & Li, X. (2019). Thermodynamic analysis of transcritical CO2 refrigeration cycle integrated with thermoelectric subcooler and ejector. Energy Conversion and Management, 188, 354–365. doi:10.1016/j.enconman.2019.02.088. [10] Astrain, D., Merino, A., Catalán, L., Aranguren, P., Araiz, M., Sánchez, D., … Llopis, R. (2019). Improvements in the cooling capacity and the COP of a transcritical CO2 refrigeration plant operating with a thermoelectric subcooling system. Applied Thermal Engineering, 155, 110–122. doi:10.1016/j.applthermaleng.2019.03.123. [11] Mohammadi, S. M. H. (2018). Theoretical investigation on performance improvement of a low-temperature transcritical carbon dioxide compression refrigeration system by means of an absorption chiller after-cooler. Applied Thermal Engineering, 138, 264–279. doi:10.1016/j.applthermaleng.2018.04.006. [12] Bellos, E., & Tzivanidis, C. (2019). Enhancing the performance of a CO2 refrigeration system with the use of an absorption chiller. International Journal of Refrigeration, 108, 37–52. doi:10.1016/j.ijrefrig.2019.09.009. [13] Nekså, P. (2002). CO2 heat pump systems. International Journal of Refrigeration, 25(4), 421–427. doi:10.1016/s0140- 7007(01)00033-0. [14] Lo Basso, G., de Santoli, L., Paiolo, R., & Losi, C. (2021). The potential role of trans-critical CO2 heat pumps within a solar cooling system for building services: The hybridised system energy analysis by a dynamic simulation model. Renewable Energy, 164, 472–490. doi:10.1016/j.renene.2020.09.098. [15] Liu, Z., Xie, N., & Yang, S. (2020). Thermodynamic and parametric analysis of a coupled LiBr/H2O absorption chiller/Kalina cycle for cascade utilization of low-grade waste heat. Energy Conversion and Management, 205, 112370. doi:10.1016/j.enconman.2019.112370. [16] Dincer, I., & Rosen, M. A. (2012). Exergy: energy, environment and sustainable development. Elsevier Science, Netherlands. doi:10.1016/C2010-0-68369-6. [17] Sarkar, J., Bhattacharyya, S., & Gopal, M. R. (2004). Optimization of a transcritical CO2 heat pump cycle for simultaneous cooling and heating applications. International Journal of Refrigeration, 27(8), 830–838. doi:10.1016/j.ijrefrig.2004.03.006. [18] Pérez-García, V., Rodríguez-Muñoz, J. L., Ramírez-Minguela, J. J., Belman-Flores, J. M., & Méndez-Díaz, S. (2016). Comparative analysis of energy improvements in single transcritical cycle in refrigeration mode. Applied Thermal Engineering, 99, 866–872. doi:10.1016/j.applthermaleng.2016.01.092. HighTech and Innovation Journal Vol. 2, No. 2, June, 2021 98 [19] Arora, A., Singh, N. K., Monga, S., & Kumar, O. (2011). Energy and exergy analysis of a combined transcritical CO2 compression refrigeration and single effect H2O-LiBr vapour absorption system. International Journal of Exergy, 9(4), 453. doi:10.1504/ijex.2011.043916. [20] Arora, A., & Kaushik, S. C. (2009). Theoretical analysis of LiBr/H2O absorption refrigeration systems. International Journal of Energy Research, 33(15), 1321–1340. doi:10.1002/er.1542. [21] Verma A,Arora A, & Mishra R S (2016). Energy Analysis and Optimization of Flat Pate Collector Area of a Solar Driven Water-Lithium Bromide Half Effect Vapour Absorption Refrigeration System for a given Cooling Load, Proceedings of The International Conference on Recent Advances In Mechanical Engineering, DTU Delhi, India, 521-528. [22] Herold, K. E., Radermacher, R., & Klein, S. A. (2016). Absorption chillers and heat pumps. CRC Press, Florida, United States. [23] Pátek, J., & Klomfar, J. (2006). A computationally effective formulation of the thermodynamic properties of LiBr–H2O solutions from 273 to 500K over full composition range. International Journal of Refrigeration, 29(4), 566–578. doi:10.1016/j.ijrefrig.2005.10.007. [24] Bejan, A., Tsatsaronis, G., and Moran, M. J. (1995). Thermal design and optimization. John Wiley & Sons, New York, United States.