International Journal of Computers, Communications & Control Vol. II (2007), No. 2, pp. 132-142 Predictive Control of a Wastewater Treatment Process Sergiu Caraman, Mihaela Sbarciog, Marian Barbu Abstract: The paper deals with the design of a predictive controller for a wastewa- ter treatment process. In the considered process, the wastewater is treated in order to obtain an effluent having the substrate concentration within the standard limits estab- lished by law (below 20 mg/l). This goal is achieved by controlling the concentration of dissolved oxygen to a certain value. The predictive controller uses a neural net- work as internal model of the process and alters the dilution rate in order to fulfill the control objective. This control strategy offers various possibilities for the control law adjustment by means of the following parameters: the prediction horizon, the control horizon, the weights of the error and the command. The predictive control structure has been tested in three functioning regimes, considered essential due to the frequency of their occurrence in current practice. Keywords: predictive control, wastewater treatment, neural network, bioreactor 1 Introduction The issue of wastewater treatment belongs to a larger area, namely the environment protection. The environment protection generally and biological wastewater treatments particularly is essential for the life of the human communities and received lately a lot of attention from specialized international orga- nizations. In this context, European laws envisage a series of specific orientations for treating and main- taining the water quality within legal limits (eg. surface water directives, 75/440/EEC and 79/869/EEC, drinking water directives 80/778/EEC/15July1980 and 98/83/EEC/3 November 1998, urban wastewater treatment directive 91/271/EEC etc.). Complementary to what has been already stated, the wastewater treatment processes are very com- plex, non-linear and characterized by many uncertainties w.r.t. the influent parameters, the structure and the coefficients of the model. Moreover, many wastewater treatment plants do not have measurement and control equipments. Therefore, there is a need in designing control strategies for the good operation of the process, strategies that may consider various types of models. Process modelling: there has been a long transition between adopting the procedure of wastewater treatment using active sludge and setting up the theoretical framework to closely describe the proce- dure. The delay was mainly caused by the conflicting hypotheses related to the explanation of process mechanisms and their difficult translation into mathematical models [3, 7]. In 1983, International Water Association (IWA) formed a working group destined to promote and facilitate the practical methods of designing and operating the biological wastewater treatment systems. As a result, the Activated Sludge Model 1 (ASM1) has been presented in 1987 (see [8]). The model used 13 state variables and described the elimination of organic carbon and nitrogen. The same working group extended the model afterwards by adding the biological process of phosphorus elimination, and named this model the Activated Sludge Model 2 (ASM2) [9]. Two other improved versions of ASM2, named ASM2d and ASM3 appeared [10]. The major shortcoming of ASM1 is its complexity, which makes it difficult to be used in a control system. A simplified alternative of the ASM1 model was obtained by taking into consideration the significant variables on a medium time-scale (a few hours to several days). This is why the variables with a slow evolution were considered constant and those having a fast evolution were neglected [13]. These simplifications allowed the usage of ASM1 model in designing control laws. Lately, IWA established two major research areas: Copyright © 2006-2007 by CCC Publications Predictive Control of a Wastewater Treatment Process 133 • Modelling of different industrial wastewater treatment processes: cellulose and paper industry, agricultural farms, spun glass industry, etc. The research team tries to model each process, de- pending on the substances involved in the process. Contrary to the case of domestic wastewater treatment which is made naturally by the microorganisms, the industrial wastewater treatment is done by cultivation of microorganisms, sometimes genetically modified, which consume a certain organic substrate [17, 5]. • Conditioning the excess of active sludge in order to use it in other industrial activities, especially as a fertilizer in agriculture [16, 20]. Process control: the wastewater treatment systems are complex, non-linear processes, with multiple inputs and outputs (multivariable), which determine equivocal information about the influent’s charac- teristics, the model’s structure and parameters. Two approaches can be distinguished in choosing the control structure for such a process: the first one is process-driven and the second one is model-based. The first approach deals with the separate control of the most important variables. Within this category, the well-known problem of controlling the dissolved oxygen level is one of the most important issues for a good operation of the wastewater treatment plants. Thus, a good level of dissolved oxygen allows the optimal growth of microorganisms used in the process [12]. Recently, the control of nitrogen and phosphor level received also a lot of attention [21]. The second approach has been improved a number of times. These improvements are related to the type of the mathematical model used, as it is the case for state estimators. Using simplified models allowed the application of advanced control techniques (e.g. precise linearizing or adaptive control, robust control techniques etc.) [19]. However, when using more complex models, such as the ASM1 model, the issue of automatic control became very complicated and the established results were less numerous. For the ASM1 model classic control techniques are usually used (PI, PID controllers), arranged hierarchically, in a three-level structure [2]: at the higher level, a stable trajectory for the process is calculated for a certain period of time; the medium level deals with the trajectory optimization for the dissolved oxygen, the flow of the recycled active sludge and the re- cycled inflow for nitrogen removal; at the lower level, the control of dissolved oxygen concentration is achieved, based on the medium level reference. A well-suited approach for this type of process is the control based on artificial intelligence strategies. Thus the intelligent control exploits the knowledge and experience accumulated from managing the process and puts it across the control structures like expert, fuzzy, neuro-fuzzy systems [1, 15, 18]. The present study considers a simplified model of the biological wastewater treatment plant [19]. The process is controlled using a model-based predictive control (MPC) strategy. The predictive controller uses a neural network as internal model of the process. This offers various possibilities for the control law adjustment by means of the following parameters: the prediction horizon, the control horizon, the weights of the error and the command. The control purpose is to maintain the substrate concentration be- low an admissible limit, which is indirectly achieved by controlling the dissolved oxygen concentration, considering as control input the dilution rate D. The predictive control structure has been tested during several functioning regimes, which are essential due to their frequent occurrence in current practice. The paper is structured as follows: the second section describes the process components and the mathematical model of the plant, the third section introduces theoretical considerations about the control structure used in the paper, while the fourth section refers to the neural network used as internal model of the predictive controller. The fifth section presents the simulation results of the proposed control structure and the last section is dedicated to conclusions. 2 The model of the wastewater treatment process The mathematical model considered in this paper has been proposed in [19]. The model is based on the following assumptions: 134 Sergiu Caraman, Mihaela Sbarciog, Marian Barbu • the system runs in steady-state regime (Fin = Fout = F , D = F/V ); • the recycled sludge is proportional to the process flow (F ): Fr = r · F , where r is the recycled sludge rate; • the flow of the sludge removed from the bioreactor (sludge that is in excess) is considered propor- tional to the process flow (F ): Fβ = β ·F , where β is the removed sludge rate; • there is no substrate or dissolved oxygen in the recycled sludge flow of the bioreactor; • the output flow of the aerated tank is equal to the sum between the output flow of the clarifier tank (settler) and the recycled sludge flow. Aerated bioreactor Settler Influent Effluent Waste sludge Settled sludge Recycled sludge S, X , DOSin, DOin, D X , DO, S, (1+r)·D Xr , r·D Xr , (r+β )·D Xr S, (1−β )·D Xr , β·D Figure 1: The schematic representation of the wastewater treatment process Figure 1 presents the schematic representation of the wastewater treatment process. The Aeration Tank is a biological reactor containing a mixture of liquid and suspended solid, where a microorganism population is grown in order to remove the organic substrate from the mixture. The Clarifier Tank is a gravity settlement tank where the sludge and the clear effluent are separated. A part of the removed sludge is recycled back to the aeration tank and the other part removed [14]. Under these conditions the process model is given by the following mass balance equations: dX dt = µ(t)X (t)−D(t)(1 + r)X (t) + rD(t)Xr(t) (1) dS dt = −µ(t) Y X (t)−D(t)(1 + r)S(t) + D(t)Sin (2) dDO dt = −K0 µ(t) Y X (t)−D(t)(1 + r)DO(t) + αW (DOmax −DO(t)) + D(t)DOin (3) dXr dt = D(t)(1 + r)X (t)−D(t)(β + r)Xr(t) (4) µ(t) = µmax S(t) kS + S(t) DO(t) KDO + DO(t) (5) where X (t) - biomass, S(t) - substrate, DO(t) - dissolved oxygen, DOmax - maximum dissolved oxygen, Xr(t) - recycled biomass, D(t) - dilution rate, Sin and DOin - substrate and dissolved oxygen concentra- tions in the influent, Y - biomass yield factor, µ - biomass growth rate, µmax - maximum specific growth rate, kS and KDO - saturation constants, α - oxygen transfer rate, W - aeration rate, K0 - model constant, r and β - ratio of recycled and waste flow to the influent. The model coefficients have the following values: Y = 0.65; β = 0.2; α = 0.018; KDO = 2 mg/l; K0 = 0.5 µmax = 0.15 mg/l; kS = 100 mg/l; DOmax = 10 mg/l; r = 0.6. Predictive Control of a Wastewater Treatment Process 135 Figure 2: The systemic diagram of the wastewater treatment process The systemic diagram of the process is given in figure 2. Figure 3 illustrates the open loop response of the system for a step input D = 0.1 h−1(W = 80 h−1). The initial conditions considered in this simulation are: X (0) = 200 mg/l, S(0) = 88 mg/l, DO(0) = 5 mg/l, X r(0) = 320 mg/l, DOin = 0.5 mg/l, Sin = 200 mg/l. 0 50 100 175 180 185 190 195 200 Time [h] X [ m g /l] 0 50 100 55 60 65 70 75 80 Time [h] S [ m g /l] 0 50 100 4.5 5 5.5 6 Time [h] D O [ m g /l] 0 50 100 320 330 340 350 360 Time [h] X r [m g /l] Figure 3: Open loop system response During the normal functioning of the wastewater treatment process, three regimes have been identi- fied: rain (D = 1/20 h−1, W = 80 h−1), normal (D = 1/35 h−1, W = 60 h−1) and drought (D = 1/50 h−1, W = 20 h−1). The first case is characterized by maximum values for the aeration and dilution rates, the second regime considers medium values for W and D and the third case is characterized by small values for the same parameters. In this study special attention has been paid to the predictive controller, such that it provides good performances for all the three functioning regimes. 3 Predictive control Predictive control algorithms belong to the class of model-based control strategies, using a process model to incorporate the predicted future behavior of the process into the controller design procedure [6]. Independent of the type of model used and of the cost index minimized, the principle of MPC is the same. At each sampling instant t [4]: • use the process model to predict the future output of the process over the prediction horizon N2 , {y(t + k/t), k = 1 . . . N2}, based on past inputs and outputs and postulated future inputs; • minimize the cost index, taking into account possible constraints on input, output and states, in order to determine the optimal control sequence {u(t + k/t), k = 0 . . . Nu −1}, where Nu is the control horizon; 136 Sergiu Caraman, Mihaela Sbarciog, Marian Barbu • use the receding-horizon control mechanism that introduces feedback into the optimization prob- lem by applying to the process the first optimal control action and discarding the consequent ones. As it is straightforward from the description above (the model is the central element of the entire strategy), the success of MPC strategy is highly dependent on a reliable process model, that is a model which approximates well the process dynamics. A lot of research has been carried out up to now in the area of MPC based on linear models, however many of the real-life processes are characterized by complex non-linearities, the necessity of having a non-linear model of the process becoming straightfor- ward. Therefore, emphasis is placed nowadays on using nonlinear models in the framework of predictive control that would lead to improved control performances. The concept of the predictive control algorithm used in this work is illustrated in figure 4. + - w u Process Model step response coefficients Min J u g(t) y y m Figure 4: Predictive control structure At each sampling instant t, the increment of the control input ∆u(t) is calculated by minimizing the cost function J = N2 ∑ k=1 δ 2(k) [w(t + k/t)−y(t + k/t)]2 + Nu−1 ∑ k=0 λ 2(k) [∆u(t + k/t)]2 (6) where w(t + k/t) is the setpoint prediction, δ (k) and λ (k) are respectively the weighting coefficients of the prediction errors and of the control input increments. In order to calculate the output prediction, the step response of the model must be determined. To this end, it is necessary to admit that the model can be linearized around the current operating point. Then y(t + k/t) = y f ree(t + k/t) + y f orced (t + k/t) (7) where { y f ree(t + k/t), k = 1 . . . N2 } is the model output produced by the control input sequence {u(t + k/t) = u(t −1), k = 0 . . . N2 −1} and y f orced (t + k/t) = k ∑ i=1 gi∆u(t + k −i/t) (8) with {gi, i = 1 . . . N2} the unit step response coefficients. In matrix notation, equation (7) becomes Y = GU + Yf ree (9) where Y = [ y(t + 1/t) . . . y(t + N2/t) ]T (10) U = [ ∆u(t/t) . . . ∆u(t + Nu −1/t) ]T (11) Yf ree = [ y f ree(t + 1/t) . . . y f ree(t + N2/t) ]T (12) G =   g1 0 . . . 0 g2 g1 . . . 0 ... ... ... ... gN2 gN2−1 . . . gN2−Nu−1   (13) Predictive Control of a Wastewater Treatment Process 137 Using the model (9) in (6), a quadratic relation with respect to U is obtained: J = [∆·W −∆(G·U + Yf ree)]T [∆·W −∆(G·U + Yf ree)] + (Λ·U )T (Λ·U ) (14) where W = [ w(t + 1/t) . . . w(t + N2/t) ]T (15) ∆ = diag [ δ (1) . . . δ (N2) ] (16) Λ = diag [ λ (0) . . . λ (Nu −1) ] (17) Only the first component of the vector U , ∆u(t/t) = ∆u(t), is used. At the next sampling instant the whole procedure is repeated. 4 The internal model of the process Artificial neural networks form an important class of nonlinear systems, with many applications in modeling and control. As mathematically proven (see [11]), any static continuous nonlinear function can be approximated arbitrary well over a compact interval by a multilayer neural network with one or more hidden layers. In this contribution a feedforward neural network is used to model the behavior of the wastewater treatment process. The proposed neural network has three layers: the first one contains 15 neurons, the second one 7 neurons and the output layer 4 neurons. To appropriately capture the interconnections be- tween all variables, up to four time-delayed values of the inputs and states were supplied to the network. The neural model predicts X (t), S(t), Xr(t) and DO(t) as functions of: D(t −1), D(t −2), D(t −3), W (t −1), W (t −2), W (t −3) X (t −1), X (t −2), X (t −3), X (t −4), S(t −1), S(t −2), S(t −3) Xr(t −1), Xr(t −2), Xr(t −3), Xr(t −4), DO(t −1), DO(t −2), DO(t −3) The data used to train the neural network was obtained by integrating the differential equations (1)- (4), considering randomly varying dilution rates in the interval [0, 0.1] and randomly varying aeration rates in the interval [0, 100]. Before training, the data was scaled to the interval [0, 1]. In the same manner, a second data set was generated and used to validate the accuracy of the model. As figure 5 shows, there is hardly any difference between the measured values from the process and the ones predicted by the neural network for the dissolved oxygen and substrate concentrations. There is a noticeable shift between the biomass calculated based on the differential equations of the process and the biomass predicted by the neural network, but this is not going to affect the performance of the predictive controller since the neural network is used to predict the dissolved oxygen level. 5 Simulation results Figure 6 illustrates the control principle. The predictive controller calculates the dilution rate, which forces the dissolved oxygen concentration to follow the setpoint. Controlling the concentration of dis- solved oxygen has a benefic effect on the substrate concentration, which is brought within the limits imposed by the law (below 20mg/l). Various configurations of the predictive controller parameters can be chosen in order to fulfill the control requirements. In these simulations a fast control was pursued, which can be generally achieved for a small prediction horizon, and less attention was paid to the magnitude of control input variations. The controller parameters were: N2 = 5, Nu = 1, ∆ = I5, λ = 0. 138 Sergiu Caraman, Mihaela Sbarciog, Marian Barbu 0 0.05 0.1 D 0 50 100 W 0 5 10 D O 0 100 200 S 0 200 400 X 0 100 200 300 400 500 600 700 800 900 1000 0 500 X r Time [h] Figure 5: Validation of the neural network model: process - continuous line, model - dash-dotted line Air flow rate (containing DO ) Consumed DO Measured DO Here intervenes the designed controller 1) If the water stays in the tank long enough, the DO concentration will increase, because the oxygen is not any longer consumed (treated water is equivalent to the substrate being biologically degraded); 2) If the water does not stay in the tank long enough, the DO will decrease, thus the water is not treated (the explanation is that aerobe metabolism reactions are taking place). Figure 6: The principle of the dissolved oxygen concentration control 0 50 100 W 4 6 8 D O 0 10 20 S 0 0.05 D 260 280 300 X 0 50 100 150 200 250 300 350 400 450 500 500 550 600 X r Time [h] Figure 7: Simulation results for DO constant setpoint (7.5) Predictive Control of a Wastewater Treatment Process 139 The results of the dissolved oxygen concentration control are presented in figures 7, 8 and 9. Figure 7 considers a constant dissolved oxygen setpoint (7.5), while figure 8 shows the case when the dissolved oxygen setpoint is variable. In both cases, the aeration rate W varies such that the process covers all three functioning regimes (rain, normal and drought). 0 50 100 W 4 6 8 D O 0 10 20 S 0 0.05 D 260 280 300 X 0 50 100 150 200 250 300 350 400 450 500 500 550 600 X r Time [h] Figure 8: Simulation results for DO variable setpoint Figure 9 considers a constant dissolved oxygen setpoint but a variable concentration of the substrate in the influent. At time t = 150 h, Sin was changed from 200 mg/l to 300 mg/l and was kept constant to the new value until t = 250 h, when it was changed to 150 mg/l. The controller adjusts the dilution rate and DO is brought back to the setpoint value. 0 50 100 W 4 6 8 D O 0 10 20 S 0 0.05 D 200 300 400 X 0 50 100 150 200 250 300 350 400 450 500 500 600 700 X r Time [h] Figure 9: Variable substrate concentration in influent 6 Conclusions Wastewater treatment is a complex process, which needs control for a good operation. This paper introduces a predictive controller for such a system and evaluates the control performances. The success of the MPC strategy is highly dependent on a reliable process model, that is a model which approximates well the process dynamics. Taking into account the complexity of the wastewater treatment process, a neural network has been chosen as internal model for the predictive controller. 140 Sergiu Caraman, Mihaela Sbarciog, Marian Barbu The simulation results show a good performance of the control loop. The controller manipulates the dilution rate and forces the dissolved oxygen concentration to follow the imposed setpoint. This has a benefic effect on the substrate concentration, which is maintained within the limits established by law. The control is effective for various operational regimes, defined by the aeration rate. Moreover, it is able to reject disturbances that might appear on the substrate concentration in the inflow. References [1] Z. Boger, Application of Neural Networks to Water and Wastewater Treatment Plant Operation, ISA Trans., Vol. 31, pp. 25-33, 1992. [2] M. A. Brdys and Y. Zhang, Robust Hierarchical Optimising Control of Municipal Wastewater Treat- ment Plants,Preprints of the 9th IFAC/IFORS/IMACS/IFIP Symposium Large Scale Systems: Theory & Applications Ű LSSŠ2001, Bucharest, Romania, pp. 540-547, July 18-20, 2001. [3] A. M. Buswell and H. L. Long, Microbiology and Theory of Activated Sludge, Journal of American Pollution Wks. Assn., Vol. 10, 1923. [4] E. F. Camacho and C. Bordons, Model predictive control, Springer-Verlag, London, 1999. [5] E. Choi et al., High strength nitrogen removal from nightsoil and piggery wastes, Proc. of the 6th IWA Speciality Symposium on Strong Nitrogenous and Agro-Wastewater, Seoul, Korea, 11-13 June, 2003. [6] R. De Keyser, Model Based Predictive Control, Invited Chapter in "UNESCO Encyclopedia of Life Support Systems (EoLSS)", EoLSS Publishers Co. Ltd., Oxford (www.eolss.net), 2003. [7] B. L. Goodman and A. J. Englande, A Unified Model of the Activated Sludge Process, Journal of Water Pollution Control Fed., Vol. 46, pp. 312-332, 1974. [8] M. Henze et. al., Activated Sludge Model No. 1, IAWQ Scientific and Technical Report No. 1, IAWQ, London, Great Britain, 1987. [9] M. Henze et al., Activated Sludge Model No. 2, IAWQ Scientific and Technical Report No. 3, IAWQ, London, Great Britain., 1995. [10] M. Henze et al., Activated Sludge Models ASM1, ASM2, ASM2d and ASM3, IWA Publishing, Lon- don, Great Britain, 2000. [11] K. Hornik, M. Stinchcobe and H. White, Multilayer feedforward networks are universal approxi- mators, Neural Networks, Vol. 2, pp. 359-366, 1989. [12] P. Ingildsen, Realising Full-Scale Control in Wastewater Treatment Systems Using In Situ Nutrient Sensors, Ph.D. thesis, Dept. of Industrial Electrical Engineering and Automation, Lund University, Sweden, 2002. [13] U. Jeppsson, Modelling Aspects of wastewater treatment processes, Ph.D. thesis, Dept. of Industrial Electrical Eng. and Automation, Lund University, Sweden, 1996. [14] M. R. Katebi, M.A. Johnson and J. Wilke, Control and Instrumentation for Wastewater Treatment Plant, Springer-Verlag, London, 1999. Predictive Control of a Wastewater Treatment Process 141 [15] R. E. King and A. Stathaki, A multi-layer perceptron for the control of a wastewater treatment plant, 12th Mediterranean Conference on Control and Automation - MED2004, Kusadasi, Turkey, Proc. CD-ROM, June 6-9, 2004. [16] H. Kroiss, What is the potential for utilizing the resources in sludge, Water Science and Technology, Vol. 49, pp. 1-10, 2003. [17] G. Langergraber et al., Monitoring of a paper mill wastewater treatment plant using UV/VIS spec- troscopy, Water Science and Technology, Vol. 49, pp. 9-14, 2003. [18] S. A. Manesis, D. J. Sapidis and R. E. King, Intelligent Control of Wastewater Treatment Plants, Artificial Intelligence in Engineering, Vol. 12, pp. 275-281, 1998. [19] F. Nejjari, A. Benhammou, B. Dahhou and G. Roux, Non-linear multivariable adaptive control of an activated sludge wastewater treatment process, Int. J. Adapt. Control Signal Process., Vol. 13, pp. 347-365, 1999. [20] J. T. Novak and C. Park, Chemical Conditioning of Sludge, Proc. of Int. Conf. on Wastewater Sludge as a Resource - Biosolids 2003, Trondheim, Norway, 23-25 June, 2003. [21] S. Yagi, H. Kohara, Y. Nakamura and S. Shiba, Fuzzy Control of a Wastewater Treatment Plant for Nutrients Removal, Proc. of the Int. Conf. on Artif. Intell. in Engineering & Technology, Sabah, Malaysia, June 17-18, 2002. Sergiu Caraman & Marian Barbu "Dunarea de Jos" University of Galati, Romania Department of Automatic Control and Electronics Domneasca Street, no. 47, 800008-Galati, Romania Sergiu.Caraman, Marian.Barbu@ugal.ro Mihaela Sbarciog Ghent University, Belgium Department of Electrical Energy, Systems and Automation Technologiepark 913, Zwijnaarde-Ghent, 9052, Belgium mihaela@autoctrl.UGent.be Received: February 19, 2007 Sergiu Caraman (born on September 30, 1955) received the Li- cense degree in 1980 from Polytechnical University of Bucharest and the PhD degree in 1996 from “Dunarea de Jos” University of Galati, Romania, both in Control Systems. Presently he is pro- fessor in the Faculty of Electrical Engineering and Electronics, “Dunarea de Jos” University. His research interest includes top- ics such as modelling and control of biotechnological processes, intelligent control. 142 Sergiu Caraman, Mihaela Sbarciog, Marian Barbu Mihaela Sbarciog(born on May 21, 1976) graduated the Faculty of Naval and Electrical Engineering of “Dunarea de Jos” Uni- versity of Galati in 1999. Presently she is a research assistant at Faculty of Engineering, Ghent University. Her main research field is the analysis and control of biochemical reaction systems. Marian Barbu (born on March 22, 1978) received the License degree in 2001 and the PhD degree in 2006 from “Dunarea de Jos” University of Galati, both in Control Systems. Presently he is lecturer in the Faculty of Electrical Engineering and Electronics, “Dunarea de Jos” University. His research interest includes topics such as modelling and control of wastewater treatment processes, robust and intelligent control.